Smart Monitoring System
Technical specifications
|
Model
|
X3-HYBRID-5.0/6.0/8.0/10.0T
|
|||
|
INPUT (DC)
|
||||
|
Max.recommended DC power[W]
|
6000
|
8000
|
10000
|
13000
|
|
MaX.DC voltage [V]
|
1000
|
|||
|
Nominal DC operating voltage [V]
|
720
|
|||
|
Max.input current [A]
|
11/11
|
20/11
|
||
|
Max. short circuit current [A]
|
14/14
|
23/14
|
||
|
MPPF voltage range [V]
|
230-800
|
|||
|
No. of MPP trackers
|
2
|
|||
|
Strings per MPP tracker
|
1
|
|||
|
OUTPUT AC
|
||||
|
Nominal AC power [VA]
|
5000
|
6000
|
8000
|
10000
|
|
Max. AC power [VA]
|
5000
|
6000
|
8000
|
10000
|
|
Rated grid voltage(AC voltage range) [V]
|
400(360 to 440)
|
|||
|
Rated grid Frequency [Hz]
|
50/60
|
|||
|
Nominal AC current [A]
|
7.6
|
9
|
12'2
|
15
|
|
Max. AC current [A]
|
8.5
|
10
|
13.5
|
16
|
|
Displacement power factor
|
0.8 leading ... 0.8 lagging
|
|||
|
Total harmonic distortion(THD, rated power) [%]
|
<2
|
|||
|
Parallel operation
|
Yes
|
|||
|
Load control
|
Yes (optional)
|
|||
|
OUTPUT DC (BATTERY)
|
||||
|
Battery voltage range [V]
|
200-500
|
|||
|
Recommended battery voltage [V]
|
200
|
240
|
320
|
400
|
|
Max.charging/discharging power [W]
|
5000
|
6000
|
8000
|
10000
|
|
Max.charging/discharging current [A]
|
25
|
|||
|
Communication interfaces
|
CAN/RS485
|
|||
|
Reverse connect protection
|
No
|
|||
|
EPS OUTPUT (WITH BATTERY)
|
||||
|
EPS rated power [VA]
|
5000
|
6000
|
8000
|
10000
|
|
EPS rated voltage [V], Frequency [Hz]
|
400/230, 50/60
|
|||
|
EPS rated current [A]
|
7.6
|
9
|
12.2
|
15
|
|
EPS peak power[W];Duration [s]
|
10000,60
|
12000,60
|
16000,60
|
16000,60
|
|
Switch time[s]
|
<0.5
|
|||
|
Total harmonic distortion(THD, linear load) [%]
|
<2
|
|||
|
Parallel operation
|
Yes
|
|||
|
EFFICIENCY
|
||||
|
MPPT effiffifficiency [%]
|
99.90
|
|||
|
Euro effiffifficiency [%]
|
97.00
|
|||
|
Max. effiffifficiency [%]
|
97.60
|
|||
|
Battery charge/discharge effiffifficiency [%]
|
96.00
|
|||
|
POWER CONSUMPTION
|
||||
|
Internal consumption(night) [W
|
<7
|
|||
|
Idle mode
|
YES
|
|||
|
STANDARD
|
||||
|
Safety
|
IEC62109-1-2 / IEC62040/ AS3100
|
|||
|
EMC
|
EN61000-6-1/EN61000-6-2/EN61000-6-3
|
|||
|
Certification
|
VDE0126-1-1 A1:2012/VDE-AR-N4105/G59-3/AS4777/EN50438/CEI 0-21/IEC62040/IEC62619/ISO13849-2/SN29500/IEC615086
|
|||
|
ENVIRONMENT LIMIT
|
||||
|
Protection class
|
Ip65
|
|||
|
Operating temperature range [ºC]
|
-25 to+60 (derating at+45)
|
|||
|
Altitude[m]
|
<2000
|
|||
|
Storage temperature[ºC]
|
-20 to+60
|
|||
|
Noise emission(typical) [dB]
|
<30
|
|||
|
Over voltage category
|
III (electric supply side), II (PV side)
|
|||
|
DIMENSION AND WEIGHT
|
||||
|
Dimensions(WxHxD) [mm]
|
650*453*222.5
|
|||
|
Weight[kg]
|
40
|
|||
|
Cooling concept
|
Natural
|
|||
|
Topology
|
Transformerless
|
|||
|
Communication
|
Ethernet, Meter, WIFI (optional), RF(optional), DRM, USB, ISO alarm, Parallel operation
|
|||
|
LCD display
|
Backlight 20*4 character
|
|||
|
Standard warranty [years]
|
5-10
|
|||