SPÉCIFICATIONS GÉNÉRALES DU TRANSFORMATEUR
|
SPÉCIFICATIONS GÉNÉRALES
|
|
|
|
TYPE DE TRANSFORMATEUR
|
|
|
Bain d'huile, hermétiquement scellé
|
INSTALLATION
|
|
|
Extérieur
|
NORMES APPLICABLES
|
|
|
CEI 60076-1
|
PUISSANCE NOMINALE
|
(ONAN)
|
KVA
|
160
|
HAUTE TENSION
|
|
KV
|
22
|
MISES EN CORRESPONDANCE HAUTE TENSION (SANS CHARGE)
|
%
|
KV
|
±2 x 2,5
|
BASSE TENSION (SANS CHARGE)
|
|
KV
|
0.4
|
NIVEAU D'ISOLATION HAUTE TENSION
|
(UM
/UAC
/ULI)
|
KV
|
24/50/125
|
NIVEAU D'ISOLATION BASSE TENSION
|
(UM
/UAC
/ULI)
|
KV
|
1 , 1 / 3 / --
|
FRÉQUENCE
|
|
HZ
|
50
|
GROUPE DE VECTEURS
|
|
|
Dyn11
|
NOMBRE DE PHASES
|
|
|
3
|
MAX. TEMPÉRATURE AMBIANTE
|
|
C
|
40
|
MAX. MONTÉE DE TEMPÉRATURE (BOBINAGE / HUILE)
|
|
C
|
65 / 60
|
MAX. ALTITUDE AU-DESSUS DE LA MER LEVELL
|
|
m
|
1000
|
DURÉE DE COURT-CIRCUIT
|
|
s
|
2
|
VALEURS GARANTIES
|
|
|
|
TENSION D'IMPÉDANCE (75 °C
)
|
tolérance de ±10%
|
%
|
6
|
AUCUNE PERTE DE CHARGE
|
tolérance de 1.5 à 5 %
|
W
|
290
|
PERTES DE CHARGE (75C)
|
tolérance de 3.5 à 8 %
|
W
|
2235
|
|
|
|
|
SPÉCIFICATIONS STRUCTURELLES
|
|
|
|
MATÉRIAUX CONDUCTEURS DE BOBINAGE HAUTE TENSION
|
|
|
Cu
|
MATÉRIAUX DE CONDUCTEUR DE BOBINAGE BASSE TENSION
|
|
|
Cu
|
TYPE D'HUILE
|
|
|
Huile du transformateur minéral inhibée
|
MATÉRIAUX DU RÉSERVOIR
|
|
|
Acier galvanisé
|
DIMENSIONS et POIDS
|
|
|
|
LONGUEUR /LARGEUR / HAUTEUR
|
|
mm
|
L / L / H
|
POIDS TOTAL
|
|
kg
|
|
POIDS DE LA PIÈCE ACTIVE
|
|
kg
|
|
POIDS DE L'HUILE
|
|
kg
|
|
|
|
|
|
BORNES DE CONNEXION
|
|
|
|
HAUTE TENSION
|
|
Manchons ProClean 30 NF 250A x 3
|
|
BASSE TENSION
|
|
Manchons ProClean 1 kV / A x 4
|
|
|
|
|
|
ACCESSOIRES
|
|
|
|
RELAIS DE PROTECTION HERMITICAL
|
|
|
|
DISPOSITIF DE DÉCHARGE DE PRESSION
|
|
|
|
CHANGEUR DE PRISES HORS CIRCUIT
|
|
|
|
PATTES DE LEVAGE
|
|
|
|
ROBINETS DE REMPLISSAGE ET DE VIDANGE D'HUILE
|
|
|
|