Overview
MNS LV withdrawable switch gear (hereinafter rferred to as device) is manufactured by standard module through consulting MNS series low voltage switch cabinet of Switzerland ABB Co-transmission, distribution, power transfer and power consumption device. It is widely used in low voltage distribution system of various mining enterprise, tall building and hotel, municipaltransmission, distribution, power transfer and power consumption device. It is widely used in low voltage distribution system of various mining enterprise, tall building and hotel, municipal construction etc. Besides the gencral land use, after special disposal, it also can be used for marine petrol drill taken platform and nuclear power station.The device accords with international standard IEC439-1 and national standard GB7251.1.
Main feature
1. Compact design: Contain more function units with less space.
2. Strong versatility for structure, flexible assembly. C type bar section of 25mm modulus can meet the demands of various structure and type, protection grade and operating environment.
3. Adopt standard module design, can be combined into protection, operation, transfer, control, regulation, measurement, indication etc such standard units. User can choose assembly according to requirement at will. Cabinet structure and drawer unit can be formed with more than 200 components.
4. Fine security: Adopt high strength antifaming type engineering plastic pack in large quantity to efctivelte enhance the protective safety performance.
5. High technical performance: Main parameters reach the advanced level at home.
Use environmental conditions
1.Altitudc above sea level should not cxcccd 2000M.
2.Ambient air temperature: -5"C~+40ºC and the average tempcrature≤+35ºCin 24h.
3.Aircondition: with elean air. Relative humidit should not exceed50% at +40C.Higherrelative humidity is allowed at lower temperature.Ex.90% at +20ºC.
4.Places without fire, explosive danger, serious pollution,chemical corrosion and fierce vibration.
5.Installation gradient not exceed 5° .
6.Control center is suitable to the transportation and store withfollowing temperature :-25ºC~-+55"C, in short time(within 24h) it should not exceed +70ºC.
The main technical parameters
Rated operating voltage(v)
|
Rated insulation voltage(V)
|
Rated operating current
|
Rated short-time withstand current
|
Enclosure protection class IP30, IP40
|
|
|
The level of bus
|
Vertical bus
|
The level of bus
|
Vertical bus
|
Height x width x depth
|
380,660
|
660,1000
|
630-5000
|
800-2000
|
50-100/105-250
|
60/130-150
|
2200x600(800,1000)x800(1000)
|
Rated working current of vertical bus bar: .
Draw-out type MCC with single side or double sides operation: 800A. MCC with 1000mm depth and single operation: 800~2000A.
Structural features
The basic cabinet of device is combined assembly structure. Basic structural pieces of cabinet is zinc plated, connected and firmed into basic bracket through self tappinglocking serew or 8.8 grade square corner screw. According to the change demand of project, aditinally add corresponding gate, closing board,bafle plate, installationsupport and the components ofbus bar, function units, to assemble a complete set of device. Perform modulus to interior component and compartment size (Modulus unite- 25mm).
Internal structure
Internal structure
Primary circuit scheme