Module Model | G M 30 |
Module Capacity | 30 KVA |
Input / Output Way | T hree phase in three phase out |
Module Dimension ( W*D*H )mm | 4 40*590*130 |
Weight (kg) | 32 kg |
Input PF | ≥0.99 |
Input Total Harmonic Distortion THDI(%) | ≤3% |
Model | 3RW G90KM30 | 3RW G150KM30 | 3RW G180KM30 | 3RW G240KM30 | 3RW G270KM30 |
Capacity |
90KVA
|
150KVA
|
180KVA
|
240KVA
|
270KVA
|
Type of power module | GM30 | ||||
Input mode | 3 Phase 4 Wire s + Ground | ||||
Input voltage (Vac) | 380V/220V±20%,400V/230V±20%,415V/240V±20% | ||||
Input Frequency (HZ) | 50Hz±10%,60Hz±10% | ||||
Input PF | ≥0.99 | ||||
Battery voltage(Vdc) | ± 240 | ||||
Charge Time | 10hs (2hs backup battery capacity) | ||||
Battery quantity(Pcs) | 32-48 can be adjusted | ||||
UPS Power Factor | 1.0 | ||||
Output Voltage (Vac) | 380/220 V ,400/230 V ,415/240 V | ||||
Output Frequency (HZ) |
50Hz±4%;Mains overrun or battery mode output is 50Hz±0.2%
60Hz±4%;Mains overrun or battery mode output is 60Hz±0.2% |
||||
Output voltage Stability |
±1%(Static);±2%(Load change from 0 ~ 100% )
|
||||
Efficiency (AC mode @ full loads) | ≥ 94% | ||||
Output voltage recovery time | <20ms(Load change from 0 - 100% ) | ||||
Overload | Rated l oad 125% , r uns 10min s | ||||
Communication function | RS232 / RS485/42 2/ dry contact / TCP/IP Expansion cards | ||||
SMMP(optional) | Can be network monitored by SNMP adapter | ||||
Parallel function | Yes(for optional) | ||||
Alarm | Battery low-voltage, mains abnormal, overload, UPS fault, over temperature protection | ||||
Working Environment Temperature | -5ºC~40ºC | ||||
IP Class | IP3 1 | ||||
Cooling | Speed controlled air cooling | ||||
Noise (dB) | ≤55dB (Within 1 meter) | ||||
Structure | 19 inch es Standard | ||||
Monitor Management System | UP Supervisor | ||||
Display | Touchable screen LCD/LED | ||||
Dimension( W*D*H ) | 600 × 800 × 1200 | 600 × 800 × 1600 | 600 × 800 × 1600 | 600 × 800 × 2000 | 600 × 800 × 2000 |
Weight ( Kg ) | 120 KG | 140 KG | 160 KG | 200 KG | 250 KG |