| TECHNICAL SPECIFICATIONS | |||||
| No. | Item | Unit | Data | ||
| 1 | Rated frequency | Hz | 50 | ||
| 2 | Rated voltage | kV | 12 | ||
| 3 | Rated current | A | 630 | 1250 | |
| 4 | Rated short-time power frequency withstand voltage | Interphase, to earth(wet) | kV/min | 34/1 | |
| Interphase, to earth(dry) | 42/1 | ||||
| Break(dry) | 48/1 | ||||
| Secondary circuit to earth | 2/1 | ||||
| 5 | Rated lightning impulse withstand voltage | Interphase, to earth | kV | 75 | |
| Break | 85 | ||||
| 6 | Rated short-circuit breaking current(virtual value) | kA | 20 | 25 | |
| 7 | Rated short-circuit making current(peak) | 50 | 63 | ||
| 8 | Rated short-time withstand current and duration | kA/s | 20/4 | 25/4 | |
| 9 | Rated peak withstand current | kA | 50 | 63 | |
| 10 | Rated short-circuit breaking current breaking times | Times | 30(E2) | ||
| 11 | SF6 gas-rated gage pressure | MPa | 0 | ||
| 12 | Main circuit resistance | μΩ | ≤120 | ||
| 13 | Rated operating voltage and rated voltage of the auxiliary circuit | V | AC/DC220,DC48,DC24 | ||
| 14 | Mechanical life | Times | 10000(M2) | ||
| Note: If the altitude is over 1000m, the rated insulation level should be modified as appropriate. | |||||