Rated voltage(V) | Poles | Rated current (A) | Rated short circuit breaking capacity | |
Test breaking capacity(KA) | Power factor | |||
230 | 1 |
6,10,16,20,25,
32, 40,50,63 |
6 | 0.75 |
400 | 2 ,3,4 | 6 |
Test current(A) | Rated current(A) | Requested time | Result | Start station | Remark |
1.13In | all | t>=1h | Don't trip | Cool | |
1.45In | All | T<1h | trip | heat | Current ascends the requested value stably in 5s |
2.55In | In<=32A | 1s<t<60s | trip | Cool | Auxiliary switch closed, power is on |
2.55In | In>32A | 1s<t<120s | trip | Cool | Auxiliary switch closed, power is on |
3 In( B mode) | All | t>=0.1s | Don't trip | Cool | Auxiliary switch closed, power is on |
5In( B mode) | All | T<0.1s | trip | Cool | Auxiliary switch closed, power is on |
5In(Cmode) | All | t>=0.1s | Don't trip | Cool | Auxiliary switch closed, power is on |
10In(Cmode) | All | T<0.1s | trip | Cool | Auxiliary switch closed, power is on |
10(Dmode) | All | t>=0.1s | Don't trip | Cool | Auxiliary switch closed, power is on |
14In(Dmode) | All | T<0.1s | trip | Cool | Auxiliary switch closed, power is on |