Type B RCCB 2pole 4 Pole 16A, 20A , 25A, 32A, 40A 63A DC Earth Leakage 10ka 300mA RCD Circuit Breaker

Model NO.
LJID 2P 4P
Poles Number
2p, 4p
Type
Circuit Breaker
Function
Conventional Circuit Breaker, Circuit-Breaker Failure Protection, Overcurrent Protection, OVP(Overvoltage Protection), RCCB
Certification
VDE, ISO9001-2000, CE, CCC
Transport Package
Paper Box Packaging
Specification
55X35X42MM
Trademark
OEM
Origin
Wenzhou
HS Code
8536200000
Production Capacity
1000PCS/Week
Reference Price
$ 50.27 - 60.17

Product Description

 
Model LJID-Type-B
Type(wave form of the earth leakage sensed) B Type RCCB
Rated current In 16A, 20A, 25A, 32A, 40A, 63A
Poles 2Pole and 4Pole
Rated voltage Ue 2Pole: 230V / 240V , 4Pole: 400V / 415V
Insulation voltage Ui 500V
Rated frequency 50/60Hz
Rated residual operation current(I n) 30mA,100mA,300mA
Rated residual making and breaking capacity (I m) 500(In=2540A) 630(In=63A)
Short-circuit current Inc= I c 10000A
SCPD fuse 10000
Break time under I n ≤0.1s
Rated impulse withstand voltage(1.5/50) Uimp 4000V
Dielectric test voltage at ind.Freq. for 1min 2.5kV
Electrical life 2,000 Cycles
Mechanical life 4,000 Cycles

Installation

Contact position indicator Yes
Protection degree IP20
Ambient temperature(with daily average≤35°C) -5°C~+40°C
Storage temperature -25°C~+70°C
Terminal connection type Cable/Pin-type busbar/U-type busbar
Terminal size top/bottom for cable 25mm 2  18-3AWG
Terminal size top/bottom for busbar 25mm 2  18-3AWG
Tightening torque 2.5Nm 22In-lbs
Mounting On DIN rail EN60715(35mm) by means of fast clip device
Connection From top and bottom

Tripping Current Range

Lagging Angle I n>0.01A I n≤0.01A
0.35I n≤I≤1.4I n 0.35I n≤I ≤2I n
90° 0.25I n≤I≤1.4I n 0.25I n≤I ≤2I n
135° 0.11I n≤I≤1.4I n 0.11I n≤I ≤2In
Detectable wave form Pulsating direct current sensitive Surge current proof
B class
Tripping is ensured for sinusoidal AC residual currents pulsed DC residual currents,alternating residual sinusoidal currents up to 1000Hz,pulsating direct residual currents and for smooth direct residual currents,whether applied suddenly or increasing slowly.
Type B RCCB 2pole 4 Pole 16A, 20A, 25A, 32A, 40A 63A DC Earth Leakage 10ka 300mA RCD Circuit Breaker
They react to AC and pulsating DC fault current which reach 0 or almost 0 within one time period of the mains frequency.
Type B RCCB 2pole 4 Pole 16A, 20A, 25A, 32A, 40A 63A DC Earth Leakage 10ka 300mA RCD Circuit Breaker
RCCB's surge capacity.
Not tripping at standardized 8/20 υs surge-current waves acc.to VDE 0432 Part 2 with surge current values of up to 250A.

Circuit Diagram
Type B RCCB 2pole 4 Pole 16A, 20A, 25A, 32A, 40A 63A DC Earth Leakage 10ka 300mA RCD Circuit Breaker

Overall and Installation Dimensions(mm)
Type B RCCB 2pole 4 Pole 16A, 20A, 25A, 32A, 40A 63A DC Earth Leakage 10ka 300mA RCD Circuit Breaker Type B RCCB 2pole 4 Pole 16A, 20A, 25A, 32A, 40A 63A DC Earth Leakage 10ka 300mA RCD Circuit Breaker Type B RCCB 2pole 4 Pole 16A, 20A, 25A, 32A, 40A 63A DC Earth Leakage 10ka 300mA RCD Circuit Breaker Type B RCCB 2pole 4 Pole 16A, 20A, 25A, 32A, 40A 63A DC Earth Leakage 10ka 300mA RCD Circuit Breaker Type B RCCB 2pole 4 Pole 16A, 20A, 25A, 32A, 40A 63A DC Earth Leakage 10ka 300mA RCD Circuit Breaker Type B RCCB 2pole 4 Pole 16A, 20A, 25A, 32A, 40A 63A DC Earth Leakage 10ka 300mA RCD Circuit Breaker

 

PNEUTEC.IT, 2023