Wd-A63 16A 20A 25A 32A 40A 50A 63A Digital Self-Resetting Under and Over Voltage Protector

Model NO.
WD-A63
Arc-extinguishing Medium
Air
Installation
Fixed
Structure
MCB
Poles Number
2
Type
Circuit Breaker
Function
Conventional Circuit Breaker, Circuit-Breaker Failure Protection, Overcurrent Protection, OVP(Overvoltage Protection), Under and Over Voltage
Certification
CE
Rated Operating
AC230V
Display
Digital
Frequency
50Hz
Electrical Life
> 100,000 Times
Rated Operating Current
10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A
Transport Package
Inner Box+Outer Carton
Specification
80*35*66mm
Trademark
Winston
Origin
Zhejiang, China
HS Code
85365000
Production Capacity
10000PCS/Month
Package Size
10.00cm * 6.00cm * 8.00cm
Package Gross Weight
0.500kg
Reference Price
$ 6.30 - 83.70

Product Description

Digital Self-Resetting Under and Over Voltage Protector

Application:

Mainly used for home and similar use of low-voltage distribution lines, when the line over voltage or undervoltage failure can automatically disconnect, and can automatically detect the line voltage, when the line back to normal when the automatic closure.
 
Products with high-speed low-power processing as the core control, high load capacity Magnetic holding relay for the main control circuit,
with online production voltage LED digital display, indicator light status indication, the product can be sustained under high pressure shock.
 
Timely protection of the safe use of load appliances. Product protection action when the neutral line is not open, in the installation should be consistent with GB16895.21 and other relevant installation procedures.

Features:
 

1. When the line undervoltage occurs in time to cut off the line, the line voltage back to normal when the delay automatically connected to the line, without human operation.
2. Line transient overvoltage or voltage sag and short interrupt, the protector does not move, to ensure reliable operation of the line. 
3. Protector itself has a high voltage withstand capacity, line fault voltage continues to 440V, the protector can safely protect the function itself will not be damaged. 
4. Effective voltage display range: 70-400V 
5. withstand the impact voltage: 5KV 
6. Outline Modulus Design: Rail mounting 
7. Wiring capacity: 16mm2 and below the wire

Specification:
Rated operating voltage AC230 / 50HZ
Rated operating current 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A
Maximum short circuit withstand current <40A 3000A,> 50A 6000A 10ms
Overvoltage action cutoff value AC275 +/- 5V
Overvoltage recovery AC255 +/- 5V
Undervoltage action cutoff value AC160 +/- 5V
Undervoltage recovery AC190 +/- 5V
Automatic closing delay after opening 25S
Action time undervoltage action time 0.8S, overvoltage action time: 0.2S-5S
Own power consumption <1.5W
Electrical machinery life > 100,000 times
Dimensions 84 * 35 * 66
Working temperature range -5 ~ 45C
Relative humidity 45 ~ 90% RH 40C
Altitude <2000
More products:
Wd-A63 16A 20A 25A 32A 40A 50A 63A Digital Self-Resetting Under and Over Voltage Protector Wd-A63 16A 20A 25A 32A 40A 50A 63A Digital Self-Resetting Under and Over Voltage Protector Wd-A63 16A 20A 25A 32A 40A 50A 63A Digital Self-Resetting Under and Over Voltage Protector Wd-A63 16A 20A 25A 32A 40A 50A 63A Digital Self-Resetting Under and Over Voltage Protector Wd-A63 16A 20A 25A 32A 40A 50A 63A Digital Self-Resetting Under and Over Voltage Protector Wd-A63 16A 20A 25A 32A 40A 50A 63A Digital Self-Resetting Under and Over Voltage Protector Wd-A63 16A 20A 25A 32A 40A 50A 63A Digital Self-Resetting Under and Over Voltage Protector

Company info:

 

PNEUTEC.IT, 2023