| Capacity | 3C10KS | 3C15KS | 3C20KS |
| Rated Power | 10000VA/8000W | 15KVA/12KW | 20KVA/16KW |
| Output Voltage | 208VAC/220VAC/230VAC/240VAC | ||
| Voltage Waveform | Pure Sine Wave | ||
| Crest Factor | 3:01 | ||
| Output Frequency (Synchronized- Mains) | 46~54Hz Or 56Hz - 64Hz (Line Mode)50/60HZ/ ±0.05Hz( Battery Mode) | ||
| Regulation(Nominal) | ±1% | ||
| Regulation (Battery Mode) | ±1% | ||
| Transfer Time | Zero | ||
| Over Current Protection | Line Mode:10min@100%~130%;Battery Mode:30s@100%~130% | ||
| Outlet | Hard Wiring With Terminal Block | ||
| Harmonic Distortion | ≤2%THD(Linear Load);≤5%THD(Non-Linear Load) | ||
| Input | |||
| Capacity | 3C10KS | 3C15KS | 3C20KS |
| Nominal Voltage | 277-520VAC@Full Load | ||
| Input Frequency | 46~54Hz / 56~60Hz | ||
| Efficiency | 90% (AC Mode) 90%(Battery Type) | ||
| Noise Filtering | Full Time EMI/RFI Filtering | ||
| Over Current Protection | By AC Fuse Or By Re-Settable Over Current Protector | ||
| AVR Range (2 Bucks,2 Boosts) | Enhanced Buck: +15% Of Selected Nominal Voltage Buck Mode: +5% Of Selected Nominal Voltage Boost Mode: -5% Of Selected Nominal Voltage Enhanced Boost: -12.5% Of Selected Nominal Voltage | ||
| Phase | Three Phase Input and Single Phase Output | ||
| Battery | |||
| Battery Type | Sealed Lead Acid Battery. | ||
| Rated Charging Voltage | Depending On The Capacity Of External Batteries | ||
| Typical Backup Time | Depending On The Capacity Of External Batteries | ||
| Charging Method | Smart Pulse Charging With Two Charging Modes. Quick Charging When Battery Is Not Fully Charged, Trickle Charging When Battery Is 90% Fully Charged. | ||
| Charging Current(MAX) | 4.0/8.0A | ||
| Protection | Over Current Protection & OverCharging Voltage Protection (SCRControl) Thermal Protection (CPU Control) When Temperature Inside UPS Is Over 45°C, Charger Will Stop Charging For 2.5 Minutes Followed By An 1.5 Minutes Charging. The Cycle Will BeRepeated Until The Temperature is Lower Than 44°C. | ||
| Temperature Compension | Yes | ||
| Numbers Of Battery | DC192V, Depending On The Capacity Of External Batteries | ||
| Optional Features | |||
| ECO Mode | Support | ||
| CVCF | Support | ||
| PDU | Support | ||
| Remote Panel | Wired Type, Up To 100M Length | ||
| Parallel Redundancy | Up To 4 Units Max (Option) | ||
| Environmental And Safety | |||
| Operating Temperature | 0 °C To 40°C (32F To 104F ) | ||
| Transit/Storage Temperature | -15°C To 55°C (5F To 131F) | ||
| Relative Humidity | 20-90%(NON-CONDENSING) | ||
| Operating Altitude | 0 ~ 3000 Meters | ||
| Audible Noise | ≤50 Dba | ||
| Safety Markings | BSMI | CE | |
| EMC | Class B, EN50091-2, FCC Part15, IEC1000-2-2 | ||
| Quality Control System | ISO 9001:2000 | ||
| Noise Level | <60db@1 Meter | ||
| Indicator | |||
| LED Version | Load Level/Battery Level/Battery Mode; AC Mode/Bypass Mode/Fault | ||
| Battery Mode | Sounding Every 4 Seconds | ||
| Low Battery | Sounding Every Second | ||
| Overload | Sounding Twice Every Second | ||
| Fault | Continously Sounding | ||
| LCD Version | Load/Battery/Input/Output/Operating;Mode Information | ||
| Interface | |||
| Smart RS-232 | Software Supports Windows Family. Sun Solaris, IBM Aix, Compaq True64,SGIIRIX ,Freebsd.HP-UX, And MAC | ||
| USB (Option) | Windows Family& MAC | ||
| Internal Slot(Option) | SNMP/AS400 Relay Card/Rs485 (Option) | ||
| EPO(Option) | Support Emergency Shutdown | ||
| Physical | |||
| Dimensions: (D×H×W)mm | 595*390*578mm | ||
| N.W/G.W (Kg) | 595*390*578mm | ||
| N.W/G.W (Kg) | 3C10KS:27 | 3C15KS:35 | 3C20KS:35 |
| Packing | Standard Packing, Export Carton For Each Unit | ||