R
oduct Over View:
1. Provide protection against earth fault/leakage current and function of isolation
2. High short-circuit current withstand capacity3. Applicable to terminal and pin/fork type busbar connection
5. Automatically disconnect the circuit when earth fault/leakage current occurs and exceeds the rated sensitivity
6. Independent of power supply and line voltage, and free from external interference, voltage fluctuation.
Specifications
Electrical
Feature |
Standard | IEC61008-1 | |
Type(wave form of the earth leakage sensed) | AC,A | ||
Rated current In | A | 16,25,32,40,63 | |
Poles | P | 2,4 | |
Rated voltage Ue | V | 230/400 | |
Rated sensitivity I n | A | 0.01,0.03,0.1,0.3 | |
Insulation voltage Ui | V | 500 | |
Rated residual making and | A | 630 | |
breaking capacity I m | |||
Short-circuit current I c | A | 4500/6000 | |
SCPD fuse | A | 6000 | |
Break time under I n | s | <0.1 | |
Rated frequency | Hz | 50/60 | |
Pollution degree | 2 | ||
MechanicaI
features |
Electrical life | t | 4000 |
MechanicaI Iife | t | 20000 | |
Fault current indicator | Yes | ||
Protection degree | IP20 | ||
Ambient temperature | C | From -25C untill 40C | |
(with daily average 35 ) | |||
Storage temperature | C | From -25C untill 70C |
Contact us
Thanks for your reading.If any product meets your need.Welcome to send us an email or by Wechat and WhatsApp.We are sure your any information can be attentioned without any delay.