Datasheet
|
||||
|
Model Name
|
MID 30KTL3-X
|
MID 33KTL3-X
|
MID 36KTL3-X
|
MID 40KTL3-X
|
|
Input AC
|
||||
|
Recommended max. PV power
|
45KW
|
49.5kW
|
54kW
|
60kW
|
|
Max. input voltage
|
1100V
|
|||
|
Rated voltage
|
600V
|
|||
|
Start-up voltage
|
250V
|
|||
|
MPPT voltage range
|
200V-1000V
|
|||
|
Max. input current
|
26A
|
|||
|
Max. short circuit current
|
32A
|
|||
|
MPPT number/Max. input strings number
|
3
|
3
|
4
|
4
|
|
Output AC
|
|
|
|
|
|
Rated output power
|
30kW
|
33kW
|
36kW
|
40kW
|
|
Max. apparent output power
|
3.3kVA
|
36.6kVA
|
39.6kVA
|
44kVA
|
|
Rated grid voltage
|
220V/380V, 230V/400V (340-440V)
|
|||
|
Rated grid frequency
|
50/60Hz
|
|||
|
Max. output current
|
50.5A
|
55.5A
|
60A
|
66.6A
|
|
Power Factor
|
0.8leading 0.8lagging
|
|||
|
THDi
|
<3%
|
|||
|
Efficiency
|
||||
|
Max. efficiency
|
98.8%
|
|||
|
EU efficiency
|
98.5%
|
|||
|
Protection
|
||||
|
DC reverse-polarity protection
|
Yes
|
|||
|
Short circuit protection
|
Yes
|
|||
|
Output over current protection
|
Yes
|
|||
|
Surge protection
|
Yes
|
|||
|
Grid monitoring
|
Yes
|
|||
|
Anti-islanding protection
|
Yes
|
|||
|
Temperature protection
|
Yes
|
|||
|
Integrated AFCI (DC arc-fault circuit protection)
|
Yes
|
|||
|
Integrated DC switch
|
Optional
|
|||
|
General Data
|
||||
|
Dimensions (W*H*D)
|
680/508/281mm
|
|||
|
Weight
|
52kg
|
|||
|
Topology
|
Transformerless
|
|||
|
Self consumption
|
<1W (night)
|
|||
|
Operating ambient temperature range
|
-25 ~ +60°C
|
|||
|
Relative humidity
|
0-100%
|
|||
|
Ingress protection
|
IP65
|
|||
|
Cooling concept
|
Natural convection
|
|||
|
Max. operation altitude
|
4000m
|
|||
|
Safety/EMC standard
|
IEC 62109-1/-2, IEC 62116, EN 61000-6-1/-2/-3/-4
|
|||
|
Features
|
||||
|
DC connection
|
H4/MC4(Optional)
|
|||
|
AC connection
|
Cable gland+OT terminal
|
|||
|
Display
|
OLED+LED/WIFI+APP
|
|||
|
Datasheet
|
|||
|
Model Name
|
12000TL3-S
|
13000TL3-S
|
15000TL3-S
|
|
Input DC
|
|||
|
Recommended max. PV power
|
14.4kW
|
15.6kW
|
18kW
|
|
Max. input voltage
|
1000V
|
||
|
Start-up voltage
|
160V
|
||
|
MPPT voltage range
|
160-1000V
|
||
|
Max. input current
|
20A/10A
|
||
|
MPPT number/Max. input strings number
|
2/2+1
|
||
|
Output (AC)
|
|||
|
Rated output power
|
12kW
|
13kW
|
15kW
|
|
Max. apparent output power
|
13.2kVA
|
14.3KVA
|
16.5kVA
|
|
AC nominal voltage
|
230V/400V 184~275V;320-478V
|
||
|
Rated grid frequency
|
50/60Hz
|
||
|
Max. output current
|
19A
|
20.6A
|
23.8A
|
|
Power Factor
|
0.8leading - 0.8laging
|
||
|
THDi
|
<3%
|
||
|
Efficiency
|
|||
|
Max. efficiency
|
98.4%
|
||
|
EU efficiency
|
98%
|
||
|
Protection
|
|||
|
DC reverse-polarity protection
|
Yes
|
||
|
Short circuit protection
|
Yes
|
||
|
Output over current protection
|
Yes
|
||
|
Surge protection
|
Yes
|
||
|
Grid monitoring
|
Yes
|
||
|
Anti-islanding protection
|
Yes
|
||
|
Temperature protection
|
Yes
|
||
|
Integrated AFCI (DC arc-fault circuit protection)
|
Yes
|
||
|
Integrated DC switch
|
Optional
|
||
|
General Data
|
|||
|
Dimensions (W*H*D)
|
575/420/225mm
|
||
|
Weight
|
30kg
|
||
|
Topology
|
Transformerless
|
||
|
Self consumption
|
<1W (night)
|
||
|
Operating ambient temperature range
|
-25 ~ +60°C
|
||
|
Relative humidity
|
0-100%
|
||
|
Ingress protection
|
IP65
|
||
|
Cooling concept
|
Natural convection
|
||
|
Max. operation altitude
|
3000m
|
||
|
Grid connection standard
|
VDE-AR-N 4105, VDE V 0124, VDE V 0126-1-1, UTE C15-712-1, NRS 097-1-2, G98, G99, EN 50549-1/-2, RD 1699, UNE 206006, UNE 206007-1, IEC 61727
|
||
|
Safety/EMC standard
|
IEC 62109-1/-2, IEC 62116, EN 61000-6-1/-2/-3/-4
|
||
|
Features
|
|
|
|
|
DC connection
|
H4/MC4(opt)
|
||
|
AC connection
|
Screw terminal
|
||
|
Display
|
LCD
|
||
|
Communication
|
RS485, Optional: Wi-Fi, GPRS
|
||
|
Datasheet
|
|||||||
|
Model Name
|
3000TL3-S
|
4000TL3-S
|
5000TL3-S
|
6000TL3-S
|
|||
|
Input DC
|
|||||||
|
Recommended max. PV power
|
3.6kW
|
4.8kW
|
6kW
|
7kW
|
|||
|
Max. input voltage
|
1000V
|
||||||
|
Rated voltage
|
620V
|
||||||
|
Start-up voltage
|
140V
|
||||||
|
MPPT voltage range
|
140-1000V
|
||||||
|
ax. input current
|
11A/11A
|
||||||
|
MPPT number/Max. input strings number
|
2/1
|
||||||
|
Output AC
|
|||||||
|
Rated output power
|
3kW
|
4kW
|
5kW
|
6kW
|
|||
|
Max. apparent output power
|
3kVA
|
4kVA
|
5kVA
|
6kVA
|
|||
|
Rated grid voltage
|
230V/400V;320-478V
|
||||||
|
Rated grid frequency
|
50Hz/60Hz,±5Hz
|
||||||
|
Max. output current
|
5.1A
|
6.8A
|
8.5A
|
10.2A
|
|||
|
Power Factor
|
0.8leading - 0.8laging
|
||||||
|
THDi
|
<3%
|
||||||
|
Efficiency
|
|||||||
|
Max. efficiency
|
97.5%
|
97.8%
|
98%
|
98%
|
|||
|
EU efficiency
|
96.5%
|
96.7%
|
96.9%
|
97.1%
|
|||
|
Protection
|
Yes
|
|
|
|
|||
|
DC reverse-polarity protection
|
Yes
|
||||||
|
Short circuit protection
|
Yes
|
||||||
|
Output over current protection
|
Yes
|
||||||
|
Surge protection
|
Yes
|
||||||
|
Grid monitoring
|
Yes
|
||||||
|
Anti-islanding protection
|
Yes
|
||||||
|
Temperature protection
|
Yes
|
||||||
|
Integrated AFCI (DC arc-fault circuit protection)
|
Yes
|
||||||
|
Integrated DC switch
|
Optional
|
||||||
|
General Data
|
|||||||
|
Dimensions (W*H*D)
|
480/448/200
|
||||||
|
Weight
|
21.2kg
|
||||||
|
Topology
|
Transformerless
|
|
|
|
|||
|
Self consumption
|
<0.5W (night)
|
||||||
|
Operating ambient temperature range
|
-25 ~ +60°C
|
||||||
|
Relative humidity
|
0-100%
|
||||||
|
Ingress protection
|
IP65
|
||||||
|
Cooling concept
|
Intelligent redundant fan-cooling
|
||||||
|
Max. operation altitude
|
3000m
|
||||||
|
Safety/EMC standard
|
IEC 62109-1/-2, IEC 62116, EN 61000-6-1/-2/-3/-4
|
||||||
|
Features
|
|||||||
|
DC connection
|
H4/MC4(opt)
|
||||||
|
AC connection
|
Connector
|
||||||
|
Display
|
LCD
|
||||||
|
Communication
|
RS485, Optional: Wi-Fi, GPRS
|
||||||
FAQ.