Digital input/output modules permit:
This provides users with the following advantages:
The SM 1223 digital input/output signal modules convert:
| SIMATIC S7-1500, CPU 1511-1 PN, Central processing unit with working memory 150 KB for program and 1 MB for data, 1. interface: PROFINET IRT with 2 port switch, 60 NS bit-performance, SIMATIC memory card necessary | |
| General information | |
| Product type designation |
CPU 1511-1 PN FS03
V2.9 |
| HW functional status | |
| Firmware version | |
| Product function | |
|
Yes; I&M0 to I&M3
Yes; Distributed and central; with minimum OB 6x cycle of 625 µs (distributed) and 1 ms (central) |
| Engineering with | |
|
V17 (FW V2.9) / V15 (FW V2.5) or higher; with older TIA Portal versions configurable as 6ES7511-1AK01-0AB0 |
| Configuration control | |
| via dataset | Yes |
| Display | |
| Screen diagonal [cm] | 3.45 cm |
| Control elements | |
| Number of keys |
8
2 |
| Mode buttons | |
| Supply voltage | |
| Rated value (DC) |
24 V
19.2 V 28.8 V Yes |
| permissible range, lower limit (DC) | |
| permissible range, upper limit (DC) | |
| Reverse polarity protection | |
| Mains buffering | |
|
5 ms
1/s |
| Input current | |
| Current consumption (rated value) |
0.7 A
0.95 A 1.9 A; Rated value 0.02 A²·s |
| Current consumption, max. | |
| Inrush current, max. | |
| I²t | |
| Power | |
| Infeed power to the backplane bus |
10 W
5.5 W |
| Power consumption from the backplane bus (balanced) | |
| Power loss | |
| Power loss, typ. | 5.7 W |
| Memory | |
| Number of slots for SIMATIC memory card |
1
Yes |
| SIMATIC memory card required | |
| Work memory | |
|
150 kbyte
1 Mbyte |
| Load memory | |
|
32 Gbyte |
| Backup | |
|
Yes |
| CPU processing times | |
| for bit operations, typ. |
60 ns
72 ns 96 ns 384 ns |
| for word operations, typ. | |
| for fixed point arithmetic, typ. | |
| for floating point arithmetic, typ. | |
| CPU-blocks | |
| Number of elements (total) | 4 000; Blocks (OB, FB, FC, DB) and UDTs |
| DB | |
|
1 ... 60 999; subdivided into: number range that can be used by the user: 1 ... 59 999, and number range of DBs created via SFC 86: 60 000
... 60 999 1 Mbyte; For DBs with absolute addressing, the max. size is 64 KB |
| FB | |
|
0 ... 65 535
150 kbyte |
| FC | |
|
0 ... 65 535
150 kbyte |
| OB | |
|
150 kbyte
100 20 20 20; With minimum OB 3x cycle of 500 µs 50 3 2 2 100 4 2 1 |
| Nesting depth | |
|
24 |
| Counters, timers and their retentivity | |
| S7 counter | |
|
2 048 |
| Retentivity | |
| - adjustable | Yes |
| IEC counter | |
|
Any (only limited by the main memory) |
| Retentivity | |
| - adjustable | Yes |
| S7 times | |
|
2 048 |
| Retentivity | |
| - adjustable | Yes |
| IEC timer | |
|
Any (only limited by the main memory) |
| Retentivity | |
| - adjustable | Yes |
| Data areas and their retentivity | |
| Retentive data area (incl. timers, counters, flags), max. | 128 kbyte; In total; available retentive memory for bit memories, timers, |
| counters, DBs, and technology data (axes): 88 KB 1 Mbyte; When using PS 6 0W 24/48/60 V DC HF | |
| Extended retentive data area (incl. timers, counters, flags), max. | |
| Flag | |
|
16 kbyte
8; 8 clock memory bit, grouped into one clock memory byte |
| Data blocks | |
|
Yes
No |
| Local data | |
|
64 kbyte; max. 16 KB per block |
| Address area | |
| Number of IO modules | 1 024; max. number of modules / submodules |
| I/O address area | |
|
32 kbyte; All inputs are in the process image
32 kbyte; All outputs are in the process image |
| per integrated IO subsystem | |
|
8 kbyte
8 kbyte |
| per CM/CP | |
|
8 kbyte
8 kbyte |
| Subprocess images | |
|
32 |
| Hardware configuration | |
| Number of distributed IO systems | 32; A distributed I/O system is characterized not only by the integration of distributed I/O via PROFINET or PROFIBUS communication modules, but also by the connection of I/O via AS-i master modules or links (e.g. IE/PB-Link) |
| Number of DP masters | |
|
4; A maximum of 4 CMs/CPs (PROFIBUS, PROFINET, Ethernet) can be inserted in total |
| Number of IO Controllers | |
|
1
4; A maximum of 4 CMs/CPs (PROFIBUS, PROFINET, Ethernet) can be inserted in total |
| Rack | |
|
32; CPU + 31 modules
1 |
| PtP CM | |
|
the number of connectable PtP CMs is only limited by the number of available slots |
| Time of day | |
| Clock | |
|
Hardware clock
6 wk; At 40 °C ambient temperature, typically 10 s; Typ.: 2 s |
| Operating hours counter | |
|
16 |
| Clock synchronization | |
|
Yes Yes Yes
Yes |
| Interfaces | |
| Number of PROFINET interfaces | 1 |
| 1. Interface | |
| Interface types | |
|
Yes; X1 2
Yes |
established in March 2016, the business scope including general management project is automation equipment accessories, instruments and meters, valves, switches, electronic semiconductor, electronic products, digital products, electronic components, communications products, computer software and hardware, security equipment, energy conservation and environmental protection products, intelligent household products; Operating electronic commerce; Domestic trade, import and export of goods and technology. Electrical automation import and export trade for the main business.
At the same time, attaches great importance to product research and development, invested a lot of funds, independent production and development of electrical equipment such as power distribution cabinet and put into use. For customers in product performance testing, automated production lines, electronic equipment, wire and cable, and other aspects of energy saving equipment reform and development, design, transform the multitude of automation equipment and automation control system, and provide a reliable and professional support, and pre-sale, sale and after-sale services - dragon, by the customer the consistent high praise.