50Hz-Three Phase-Power Factor 0.8 |
|||
|
Rating |
Prime Power |
Standby Power |
Rated Current |
|
Voltage (V) |
KVA/KW |
KVA/KW |
(Amp) |
|
220V/380V |
80/100 |
88/110 |
152.0 |
|
230V/400V |
80/100 |
88/110 |
144.3 |
|
240V/415V |
80/100 |
88/110 |
139.1 |
|
Engine Specification General Performance |
|
|
Engine Model: |
6BT5.9-G2 |
|
Engine Type: |
4 cycle, In-line, 6-cylinder |
|
Engine Speed: |
1500 r.p.m |
|
Base Output Power: |
86kW/115hp |
|
Standby Power: |
92kW/123hp |
|
Governor Type: |
Electronic |
|
Air Intake Way: |
Turbocharged & After-cooled |
|
Displacement: |
5.9L |
|
Cylinder Bore * Stroke: |
102mm x 120mm |
|
Compression Ratio: |
17.3:1 |
|
Coolant Capacity Engine Only |
7.9 Litres |
|
Alternator Specification General Performance |
|
|
Engine Model: |
Stamford UCI274C /Leroy-somer LSA44.2VS45 |
|
Phase |
3 Phase |
|
Power Factor |
0.8 |
|
Drip Proof |
IP 23 |
|
Insulation class |
H |
|
Voltage regulation |
± 0,5 % |
|
Altitude |
≤ 1000 m |
|
Over speed |
2250 min -1 |
|
Scope of supply |
|
|
Standard |
Optional |
|
High efficient water cooled diesel engine |
Automatic Transfer Switch (A.T.S) |
|
Brushless alternators (Class H, with AVR.) |
Water - Fuel separator |
|
Heavy duty rubber anti-vibration mountings |
Water heater for severe cold weather |
|
24V starter batteries and connecting cables |
Lub-oil heater for severe cold weather |
|
Industrial silencer |
Low coolant level sensor |
|
Auto start Digital Control Panel |
Dual wall base fuel tank |
|
Radiator with cap and drain point |
Fuel level sensor |
|
Fully guarded engine driven fan |
ABB brands Breakers |
|
Circuit Breaker |
Separated standing fuel tank |
|
Soundproof canopy for silent genset |
Alternator Space Heater |
|
Oil filter - Diesel filter - Air filter |
DSE6020,DSE7320,ComAp AMF25 controller |
|
50ºC Radiator |
Customized 24H,48H base fuel tank |