Output
|
Parameter
|
Min.
|
Typ
|
Max.
|
Unit
|
Remarks
|
Inverter Output
|
Rated voltage
|
|
220
|
|
Vac
|
Full input range
|
Rated current
|
|
4.6
|
|
A
|
|
Voltage
accuracy
|
|
|
±
5
|
%
|
Full input range
|
Rated Frequency
|
49
|
50
|
51
|
Hz
|
|
Rated capacity
|
|
|
1000
|
VA
|
|
Rated power
|
|
|
1000
|
W
|
|
Efficiency
|
85
|
|
|
%
|
Rated working condition
|
Power factor
|
0.8
|
|
|
|
Rated working condition
|
Dynamic transient recovery time
|
|
|
60
|
ms
|
|
Waveform
|
Sine wave THD
<
3%
(
linear load
)
|
Sine waveTHD
<
8%
(
non-linear load
)
|
Overload capacity
|
105~125% load for more than10 mins, 125~150%load for more than10 secs.
|
Output current peak ratio
|
3
:
1
|
Output QTY
|
Two AC outputs
|
Bypass AC output
|
Output voltage range
|
200
|
|
240
|
Vac
|
Changes according to AC voltage's changing.
|
Rated voltage
|
|
220
|
|
Vac
|
|
Rated current
|
|
|
5
|
A
|
|
Inverter switches to grid's time.
|
|
|
20
|
ms
|
Rated load
|
Grid switches to inverter's time.
|
|
|
100
|
ms
|
Rated load
|
Output description
|
Share the same output terminals to the inverter. When there is AC input, use the grid. When AC fail, automatically switch to the inverter and then power the equipments.
|