Model |
Q6K | Q6KL | Q10K | Q10KL | 31Q10KL | 31Q15KL | 31Q20KL | |
| Capacity | 6KVA/4800W | 10KVA/8000W | 15KVA/12KW | 20KVA/16KW | ||||
| Input | Nominal Voltage | 220/230/240Vac | 380/400/415Vac | |||||
| Voltage Range | 176~276Vac (1P2W+G) | 304~478Vac (3P4W+G) | ||||||
| Current | 31A (max) | 50A (max) | 50A (max) | 75A (max) | 100A (max) | |||
| Frequency | 46~54Hz/56~64Hz | |||||||
| Power Factor | ≥ 0.99 | |||||||
| Output | Voltage | 220/230/240± 2%Vac (1P2W+G) | ||||||
| Frequency | 50/60Hz(adjustable) 50/60Hz± 5% (Line mode) 50/60Hz ± 0.05Hz ( Battery mode) | |||||||
| Current | 27.3A | 45A | 68A | 91A | ||||
| Power Factor | 0.8lag | |||||||
| Waveform | Pure Sine Wave | |||||||
| Waveform Distortion | Line load < 2% | Line load < 3% | ||||||
| Back-up Time | Full Load | ≥ 7 ′ | Depends on external batteries bank's Capacity | ≥ 5 ′ | Depends on external batteries bank's Capacity | |||
| Half Load | ≥ 20 ′ | ≥ 13 ′ | ||||||
| Battery Nominal Voltage | 192/240Vdc | |||||||
| Transfer Time | 0ms | |||||||
| Overload Capacity | > 105% 1min, > 120% 30s transfer to bypass, shut down in 1min | |||||||
| Communication | SNMP,RS-232,USB+Intelligent Slot | |||||||
| Operating Environment | Temperature | 0C~40 Centi Degree | ||||||
| Humidity | 15%~90% | |||||||
| Dimension | Width (mm) | 260 | 260 | 260 | 260 | 260 | ||
| Depth (mm) | 560 | 533 | 560 | 533 | 560 | |||
| Height (mm) | 717 | 501 | 717 | 501 | 717 | |||
| Net Weight(Kg) | 68 | 18 | 70 | 20 | 28 | 30 | 30 | |
| *Specification are subject to change without prior notice | ||||||||