high voltage pulse generator
|
XHHV535-4TS
|
0-35KV,2048J, 8/16/32KV, boosting,breakdowm fault cable and discharging to fault cable
|
Cable fault pre-locator
|
XHGG501A
|
measuring underground cable fault rough distance
|
cable route tracer
|
XHLJ504L
|
For underground cable pipe locating
|
cable fault pinpointer
|
XHDD 503
|
For underground cable fault pinpointing detection
|
Product Description
XZH TEST Portable cable fault location system is designed for:
★
XHHV535-4TS High voltage 2048 J surge generator is accompanied by a surge levels switch which allows to achieve the maximum surge impulse energy at 8, 16 and 32 kV. It has features operator safety assurance systems and provides a reliable and comprehensive technical solution for low- and medium-voltage cables faults.
★Cable fault pre-locator: XHGG501A In general, low resistance and open circuit faults (high resistance) can be judged directly by means of an ohm meter or the "pulse method" test waveform of the "cable fault flash tester".
★cable route tracer: XHLJ504L A special instrument for accurately detecting the location of buried cable paths and burial depths within a certain range; Path detection is accomplished by the path signal generator and path signal receiver working in conjunction with the test; through their operation in conjunction with each other, the cable path is precisely located within the approximate cable burial range.
★cable fault pinpointer: XHDD 503 cable fault locator (conventional) is experienced in the use of the acoustic-magnetic
synchronisation principle with double discriminations. It is mainly used for the precise localisation of fault points within the coarse measurement of faults and directly above the faulty cable.
cable fault prelocator XHGG501B
|
Testing method
|
current and voltage method, inductive sampling method, flash sampling method, low-voltage pulse method
|
Sampling rate
|
25/50/100MHz
|
Testing distance
|
≤30km Resolution:0.5m
|
Low-voltage pulse
|
amplitude: 100Vpp
|
width
|
0.1/2μs
|
Display operation
|
5 inch two-colour screen, key operation
|
Communication mode
|
RS232 panel micro print test report
|
Built-in power supply
|
can work continuously for 20 hours, also can work with external AC power supply
|
Working conditions
|
Temperature -20ºC~+45ºC, relative humidity 90%
|