| Model | ND220-1010 | ND220-1020 | ND220-1030 | ND220-1050 | ND220-1060 | ND220-1100 | ND220-1150 | ND220-1200 | ND220-1300 | |
| DC-ingang | ||||||||||
| Nominale ingangsspanning | 220 VDC | |||||||||
| Nominale ingangsstroom | 4.5A | 9 A. | 13, 5A | 22 A. | 27 A. | 45 A. | 74, 2 A | 99 A. | 149 A. | |
| DC-ingangsspanningsbereik | 180 ~ 260 VDC | |||||||||
| Bypass Utility-invoer | ||||||||||
| AC-ingangsspanning | 220 V AC±20%, 50 Hz±10% | |||||||||
| Nominale ingangsstroom | 4.5A | 9 A. | 13, 5A | 22 A. | 27 A. | 45 A. | 67, 5A | 90 A. | 135 A. | |
| Overdr. Tijd overslaan | ≤4 ms | |||||||||
| AC-uitgang | ||||||||||
| Nominale capaciteit | 1 KVA | 2 KVA | 3 KVA | 5 KVA | 6 KVA | 10 KVA | 15 KVA | 20 KVA | 30 KVA | |
| Nominaal uitgangsvermogen | 0, 8 KW | 1, 6 KW | 2, 4 KW | 4 KW | 4.8KW | 8 KW | 12 KW | 16 KW | 24 KW | |
| Nominale uitgangsspanning en frequentie | 220 V AC, 50 Hz | |||||||||
| Nominale uitgangsstroom | 4.5A | 9 A. | 13, 5A | 22 A. | 27 A. | 45 A. | 67, 5A | 90 A. | 135 A. | |
| Regeling uitgangsspanning | 220 V AC±2% | |||||||||
| Regeling uitgangsfrequentie | 50 Hz±0, 25 Hz | |||||||||
| THD | ≤3% | |||||||||
| Dynamische respons (belasting 0→100%) | 5% | |||||||||
| Arbeidsfactor | 0.8 | |||||||||
| Overbelasting | 150%, 60 jaar | |||||||||
| Crest-factor | 3: 01 | |||||||||
| Rendement bij nominale belasting | 90% | |||||||||
| Milieu | ||||||||||
| Isolatiesterkte (tussen ingang en Uitgang) | 1500 VAC, 1 min. | |||||||||
| Geluid (1 m) | ≤50 dB | |||||||||
| Temperatuur | -10ºC~+50ºC | |||||||||
| Vochtigheid | 0~90%, geen condensatie | |||||||||
| Hoogte (m) | ≤2000 | |||||||||
| Fysiek | ||||||||||
| Afmetingen (B* D * H, mm) | 440 × 450 × 133 | 440 × 450 × 177 | 440 × 500 × 221.5 | 343*630*700 (240*540*680 voor 6K) | ||||||
| Type | Type rek | Type toren | ||||||||
| Bescherming | Beveiliging van DC-ingang tegen omdraaien, DC-ingang onder spanning, overspanning, overbelasting, kortsluiting, te hoge temperatuur | |||||||||