| Battery Pack Performance Specifications | |
| | Rated voltage | 51.2V | |
| |
| | Rated capacity | 100Ah | |
| | Rated energy | 5120Wh | |
| | maximum continuous | 5kW | |
| | power |
| | Maximum number of parallel connections | | |
| | RS485: 15 | |
| | Series connection | Prohibit | |
| | BMS Model | 16S100A | |
| | | Over-charge protection;Over-discharge | |
| Electrical Characteristics | BMS Function | protection;Over-current protection;short | |
| | | circuit protection;Temperature protection | |
| | | and balance function | |
| | Heating Function | Optional | |
| | Communication | RS232;RS485;CAN (Optional) | |
| | Cycle life | ≥2000 cycles (0.5Ccharge and discharge, | |
| | 80%DOD ,60%EOL ,25C) | |
| | Equalizing voltage | 56V | |
| | Float voltage | 55.2V | |
| | Standard charging | 20A/1000W | |
| Charging characteristics | current/power |
| | Max charging | 50A/2500W | |
| | current/power |
| | Standard discharging current/power | 20A/1000W | |
| | Max discharging | 100A/5000W | |
| Discharging characteristics | current/power |
| | Discharge end of voltage | 43.2V | |
| | Size (W×D×H) mm | 440×470×156 (19inch 3.5U) | |
| | Shell material | metal housing | |
| Mechanical characteristics | Weight | About 50Kg | |
| | Waterproof Rating | IP20(indoor use ) | |
| Temperature | Charge temperature | 0C to 50C | |
| characteristics | Discharge temperature | -20C to 55C | |
| | Best performance | 10C to 40C | |
| temperature |
| | Storage temperature | ≤ 35C,50%SOC ,6 months | |
| BMS parameters | |
| No | | | The reference standard (the |
| Item | Detail | set value is subject to the |
| | | actual set value) |
| | | Cell overcharge alarm voltage | 3.50~3.90V |
| | Overcharge | Overall overcharge alarm voltage | 56.40V~57.60V |
| 1 | protection | Cell overcharge protection voltage | 3.50~3.90V |
| | | Overall overcharge protection voltage | 56.40V~57.60V |
| | | Cell over discharge alarm voltage | 2.0V~2.90V |
| | Over discharge protection | Overall over discharge alarm voltage | 36.00V~48.00V |
| 2 | | Over discharge protection voltage | 2.0V~2.90V |
| | | Overall over discharge protection voltage | 36.00V~48.00V |
| | | Protection conditions | External circuit short circuit |
| | |
| | |
| | Short circuit protection | Delay time | ≤1mS |
| 3 | | | Cut load. If a short circuit is |
| | | | triggered multiple times, it is |
| | | Release condition | locked into a protected state. |
| | | | After the user needs to check |
| | | | the external circuit, reset the |
| | | | BMS and release the protection. |
| | | Battery high temperature warning | 35C~65C |
| | Temperature protection | Battery high temperature protection | 35C~65C |
| 4 | | Battery low temperature warning | -20C~0C |
| | | Battery low temperature protection | -20C~0C |
| | | Balance turn-on voltage | 3 45V±0 02V |
| 5 | Charge balance | Balance turn-on voltage difference | 20mV |
| | | Balance current | 85mA±20mA |
| 6 | Communication | RS232/RS485 | Default baud rate is 9600bit/S |
| | Power | Circuit consumes current while working | ≤50mA |
| 7 | consumption | Sleep mode consumes current | ≤300 μA |