Sequence
NO . |
Release |
Test
current I/In |
Start state |
Tripping
time |
Expected
restlt |
| 1 | c | 1.13In | Cold state | t≤1h | Not tripping |
| 2 | c | 1.45In |
Start right after
the serial NO . 1 test |
t<1h | Tripping |
| 3 | c | 2.55In | Cold state | 1s<t<60s | Tripping |
| 4 | c | 5In | Cold state | t≤0.1s | Not tripping |
| 5 | c | 10In | Cold state | t<0.1s | Tripping |
| Frame class | 63A |
| Rated working voltage | 240V/415V |
| Rated frequency | 50/60Hz |
| Rated working current | 6,10,16,20,25,32,40,50,63A |
| Making and breaking capacity | 10000A |
| Release type | C |
| Poles | 1,2,3,4P |
| Mechanical life | 10000 |
| Electric life | 4000 |