| Technical Data | Austa-1P3.6K1G | Austa-1P5K1G | Austa-1P6K1G | Austa-1P8K1G |
| Energy source | Grid-connected PV | |||
| Description | 5kva 6kw Solar dc to ac Power home Grid Tie Inverter | |||
| Input Side | ||||
| Max.DC Input Power(kW) | 4.68 | 6.5 | 6.6 | 8.8 |
| Max.DC Input Voltage(V) | 500 | 500 | 500 | 500 |
| Start-up DC Input Voltage(V) | 120 | 120 | 120 | 120 |
| MPPT Operating Range(V) | 100-500 | 100-500 | 100-500 | 100-500 |
| Max.DC Input Current(A) | 13+13 | 13+13 | 13+13 | 13+26 |
| Number of MPPT/String per MPPT | 2/1 | 2/1 | 2/1 | 2/1+2 |
| OutPut Side | ||||
| Rated Output Power(kW) | 3.6 | 5 | 6 | 8 |
| Max.Active Power(kW) | 4 | 5.5 | 6.6 | 8.8 |
| Rated AC Grid Voltage(V) | 230 | 230 | 230 | 230 |
| AC Grid Voltage Range(V) | 180-300 | 180-300 | 180-300 | 180-300 |
| Rated Grid Frequency(Hz) | 50/60(Optional) | 50/60(Optional) | 50/60(Optional) | 50/60(Optional) |
| Operating Phase | Single Phase | Single Phase | Single Phase | Single Phase |
| Rated AC Grid Output Current(A) | 16 | 22 | 26 | 35 |
| Max.AC Output Current(A) | 18 | 24 | 29 | 39 |
| Output Power Factor | 0.8 leading to 0.8 lagging | |||
| Grid Current THD | <3% | <3% | <3% | <3% |
| DC Injection Current(mA) | <0.5% | <0.5% | <0.5% | <0.5% |
| Grid Fequency Range | 47-52/57-62(Optional) | 47-52/57-62(Optional) | 47-52/57-62(Optional) | 47-52/57-62(Optional) |
| Efficiency | ||||
| Max.Efficiency | 97.3% | 97.5% | 97.5% | 97.7% |
| Euro Efficiency | 97.1% | 97.3% | 97.3% | 97.5% |
| MPPT Eifficiency | >99% | >99% | >99% | >99% |
| Protection | ||||
| Anti-islanding Protection | Integrated | |||
| DC Reverse-Polarity Protection | Integrated | |||
| DC Surge Protection | Integrated(Type II) | |||
| AC Surge Protection | Integrated(Type II) | |||
| AC Short Circuit Protection | Integrated | |||
| AC Output Overcurrent Protection | Integrated | |||
| Output Overvoltage Protection | Integrated | |||
| AC Grid Monitoring | Integrated | |||
| Ground Fault Monitoring | Integrated | |||
| Insulation Resistance Protection | Integrated | |||
| Residual Current Monitoring Unit | Integrated | |||
| Temperature Protection | Integrated | |||
| Integrated DC Switch | Optional | |||
| General Data | ||||
| Size(mm) | 330W*310H*172D | |||
| Weight(kg) | 11 | |||
| Topology | Transforemerless | |||
| Internal Consumption | <1W(Night) | |||
| Running Temperature | -25-60ºC | |||
| Ingress Protection | IP65 | |||
| Noise Emission(Typical) | <30dB | |||
| Cooling Concept | Intelligent cooling | |||
| Max.Operating Altitude Without Derating | 2000m | |||
| Designed lifetime | >20years | |||
| Operating Surroundings Humidity | 0-100% | |||
| Features | ||||
| DC Connection | MC-4 mateable | |||
| AC Connection | IP65 rated plug | |||
| Display | LCD1602 | |||
| Interface | RS485/RS232 | |||
| Certifications&Standers | ||||
| Grid Regulation |
IEC61727/ 62116/
60068 /61683/ INMETRO (ABNTNBR 16149/ 16150) |
IEC61727/ 62116/ 60068/ 61683 | IEC61727/ 62116/ 60068/ 61683 | INMETRO (ABNTNBR 16149/ 16150) /IEC62116 |
| Safety Regulation | IEC /EN62109-1/2 | |||
| EMC Regulation | IEC /EN61000-6-1 /61000-6-3 | |||