High Precision Portable CT PT Analyzer 0.02% / 0.05% Ratio Error with Printer

Model NO.
GF106T
Current Output
0-5A
Thermocouple (TC)
R
LCD Display
With LCD Display
Customized
Customized
CT Raito
1-50000
Ratio Error
0.02% or 0.05%
Weight
4kg
PT Ratio
1-10000
Usage
Measurement CT and Protection C
Phase Error
1min or 3min
Theory
DC Variable-Frequency Methods
Name
CT PT Analyzer
Transport Package
Standard Carton Packaging
Specification
7inch TFT Touch Color LCD
Trademark
PAX
Origin
Beijing, China
HS Code
8480410090
Production Capacity
1000sets/Month
Reference Price
Please contact us for quote

Product Description

Detailed Product Description High Precision Portable CT PT Analyzer 0.02% / 0.05% Ratio Error with Printer

 
Name:CT PT AnalyzerApplication:Current Transformer And Potential Transformer Test
Theory:DC Variable-frequency MethodsLCD:7inch TFT Touch Color LCD
Phase Error:1min Or 3minRatio Error:0.02% Or 0.05%
CT Raito:1-50000PT Ratio:1-10000
Usage:Measurement CT And Protection CTWeight4KG

GF1061 portable CT PT analyzer is mainly used for field or lab testing, it can finish the measurements (M) and protection (P) class CT, PT and TYP class CT. Adopt 7 inch touch TFT LCD, self-equipped mini type printer supporting field printing; supporting to use USB flash disk to dump data. The CT PT Analyzer is the most complete and easy-to-use testing system for protection and metering CTs according to IEEE and IEC standards.
The CT Analyzer automatically determines all relevant current transformer values and compares the results with the selected standard. The device evaluates the current transformer as per the IEC or IEEE standard within seconds with the push of a button. its can test current transformer and potential transformer ratio error and phase error, Magnetization curve etc
It facilitates fast and economical on-site testing and calibration of metering and protection current transformers. Manufacturers of current transformers, high voltage transformers and switchgear also use the CT Analyzer for tests during development and production.

Application

1. Measurement type current transformer
2. Protection type current transformer
3. GIS type current transformer
4. Bushing type current transformer
5. Zero sequence current transformer
6. Voltage transformer

MAIN FUNCTIONS

I. Current Transformer (CT)II. Voltage Transformer (PT)
1. Magnetization curve1. Excitation characteristic test
2. Transformation ratio test2. Transformation ratio test
3. Polarity3. Polarity
4. 5% and 10% error curve4. Ratio error, phase error
5. Accuracy limiting factor (ALF)5. Degauss
6. Degauss6. Calculation of knee point value
7. Ratio error, phase error7. Actual secondary load test (burden test)
8. Automatic calculation of excitation knee
point value
8. Resistance test
9. Actual secondary load test (burden test)
10. Resistance test
11. Secondary time constant (Ts)
12. Remanence coefficient (Kr)
13. Transient dimensioning factor (Ktd)
14. Peak instantaneous error (Er)
15. Magnetizing inductance (LU)
16. Instruments security factor(FS)
17. Composite error

 

 

PARAMETERS

 
 
Electrical parameters
Accuracy0.05%, 0.02%
Power supplyAC 220V±10% or AC 120V±10%, 50/60Hz or Battery
Output voltage0-100Vrms
Output current0-5Arms (20A peak-value)
Output power0-400 VA (1500 VApeak)
Automatic frequency variation range0.1-60Hz
Equivalent excitation voltage≤5000V
Accuracy≤0.5%
Secondary winding DC resistance measurementRange0.1-1000Ω
Accuracy≤0.05%
Secondary actual load measurementRange5VA-1000VA
Accuracy≤0.5%±0.1VA
CT/PT phase error measurementAccuracy±1min (typical) / 3 min (guaranteed)
Resolution0.1min
CT ratio error measurementRange1-50000
Accuracy≤0.05%
PT ratio error measurementRange1-10000
Accuracy≤0.05%
Standards
Reference standardsGB1207-2006, GB1208-2006, GB16847-1997
IEC60044-1, IEC60044-6, IEC61869-2, ANSI/IEEE C57.13
Safety standardsGB 4793.1-2007
EMCEMC standard 89/336/EEC
FCC Subpart B of Part 15 Class A
IEC 1000-4-2 /3 /4 /6
Mechanical parameters
Overall dimension (L x W x H) (mm)280 x 250 x 160
Weight (kg)≤4
Environmental conditions
Relative humidityRelative humidity 5%-95% not condensing
Operating temperature-10°C to +50°C
Storage temperature-20°C to +70°C
Altitude≤1000m
 

 

Calibrator