Relay Protective Device with Over Current Protection Overload

Poles Number
2
Type
Circuit Breaker
Function
Conventional Circuit Breaker, Circuit-Breaker Failure Protection, Overcurrent Protection, OVP(Overvoltage Protection)
Certification
ISO9001-2000, CE, CB, CCC
Rated Operating Voltage
AC230V
Frequency
50Hz
Rated Operating Current
10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A
Transport Package
Standard Export Packing
Specification
51*35*60mm
Trademark
HANDELE
Origin
China
HS Code
8536500000
Production Capacity
10000PCS/Month
Reference Price
$ 2.70 - 4.50

Product Description

1.General Introduction

The multifunctional self-resetting dual display protector integrates over-voltage protection, under-voltage protection, over-current protection and integrated intelligent protector. When there is over-voltage, under-voltage and over-current solid barriers in the line, this product can instantly cut off the circuit, avoiding unnecessary damage to electrical equipment. When the circuit returns to normal, the protector can automatically restore the circuit to make the electrical equipment work normally. The overvoltage value, undervoltage value, overcurrent value, circuit recovery time value and overcurrent protection reset time value of this product can be set by themselves. Adjust the corresponding parameters according to local actual conditions and electrical usage conditions.
Relay Protective Device with Over Current Protection Overload Relay Protective Device with Over Current Protection Overload Relay Protective Device with Over Current Protection Overload Relay Protective Device with Over Current Protection Overload
 
2.   Product   features

2.1   The   product   fully   conforms   to   the   single-phase   self-reclosing   recloser   produced   by   the   enterprise
standard.
2.2   When   the   line   has   overvoltage,   undervoltage   and   overcurrent   faults,   the   product   will   automatically   cut
off   the   line.   When   the   line   voltage   or   current   returns   to   normal,   the   product   will   automatically   resume
normal   power   supply   after   the   delay   time   set   by   the   user.
No,   manual   operation   is   required.
2.3   When   the   line   appears   instantaneous   or   transient   overvoltage,   the   protector   does   not   malfunction.
2.4   The   line   voltage   is   unstable   or   the   power   is   suddenly   cut   off   due   to   some   factors,   when   the   power
recovers,   the   product   will   not   connect   to   the   power   immediately.   This   delay   time   is   set   by   the   user
according   to   the   local   situation.
2.5   The   line   voltage   should   not   be   higher   than   330vac   to   prevent   the   product   itself   from   being   damaged
due   to   excessive   voltage.   Please   contact   the   manufacturer   if   a   high   power   supply   is   required   in   a   specific
situation.


3.   Normal   usage   conditions

3.1   The   ambient   temperature   does   not   exceed   +50   degrees   and   not   less   than   -10   degrees.
3.2   The   altitude   of   the   installation   site   does   not   exceed   2000   meters
3.   3   Humidity:   not   more   than   60%
3.4   Pollution   degree   3


4.   Installation   conditions

4.   1   The   protector   can   be   installed   vertically   or   horizontally   in   the   cabinet,   and   special   orders   are   required
for   special   occasions.
4.2   It   should   be   installed   in   a   non-explosive   medium,   and   there   is   no   sufficient   fermented   bean   curd   metal
and   insulating   gas   and   conductive   dust   in   the   medium.
4.3   It   should   be   installed   in   a   place   where   there   is   no   rain   or   snow.


5.   Main   technical   parameters

5.1   Rated   voltage:   220VAC   50Hz.
5.2   Rated   current:   1A-63A   adjustable   (default   40A)
5.3   Overvoltage   action   cut-off   value:   240V-300VAC   can   be   set   (default   270VAC)
5.4   Overvoltage   action   cut-off   value:   140V-200VAC   can   be   set   (default   1   70VAC)
5.5   Overcurrent   action   cut-off   value:   63A:   1A-63A   can   be   set   (default   40A)   /   40A:   1   A-40A   can   be   set
(default   40A)
5.6   Transmission   delay   time   after   power-on   and   power-off:   5-300S   adjustable   (default   5S)
5.7   Boot   delay   time:   1-300S   adjustable   (default   5S)
5.8   Reset   delay   time   after   overcurrent   protection:   30-300s   adjustable   (default   30s)
5.9   Product   overcurrent   delay   time   6s   (overcurrent   time   greater   than   this   time   will   be   confirmed   as
overcurrent   and   provide   protection)
5.10   Own   power   consumption:   less   than   or   equal   to   2W
5.11   Electrical   machinery   life:   greater   than   or   equal   to   100,000   times
5.12   Dimensions:   51*35*60mm
Rated voltage 220VAC 50Hz
Rated current 1A-63A adjustable (default 40A)
Overvoltage action cut-off value 240V-300VAC can be set (default 270VAC)
Overvoltage action cut-off value 140V-200VAC can be set (default 1 70VAC)
Overcurrent action cut-off value 63A: 1A-63A can be set (default 40A) / 40A: 1 A-40A can be set (default 40A)
Transmission delay time after power-on and power-off 5-300S adjustable (default 5S)
Boot delay time 1-300S adjustable (default 5S)
Reset delay time after overcurrent protection 30-300s adjustable (default 30s)
Product overcurrent delay time 6s (overcurrent time greater than this time will be confirmed as overcurrent and provide protection)
Own power consumption less than or equal to 2W
Electrical machinery life greater than or equal to 100,000 times

6.   Product   setting Relay Protective Device with Over Current Protection Overload

7.   Use

After   the   protector   is   installed,   the   user   can   wire   it,   and   select   the   wire   section   that   meets   the   standard
according   to   the   setting   current   of   the   protector.   Note   that   the   input   and   output   wires   of   the   protector
cannot   be   connected   incorrectly   to   avoid   damage   to   the   product   or   power   failure.


8.   Precautions

8.   1   When   performing   various   current   operation   or   tests,   users   should   follow   the   relevant   regulations   and
pay   attention   to   the   following   matters   to   ensure   the   correct   and   safe   use   of   this   product.

8.2   According   to   the   product   standard,   the   input   and   output   terminals   are   connected   correctly   (the   load
current   should   be   less   than   the   protection   current   value   of   the   product)
8.3   The   neutral   wire   N   cannot   be   connected   wrongly   and   must   be   connected   reliably,   otherwise   the
protector   cannot   work   normally.
8.   4   Before   turning   on   the   power,   carefully   check   whether   the   wiring   is   correct,   whether   the   load   size
matches   the   current   protection   value   of   the   product,   and   whether   the   wiring   screws   are   tightened,
otherwise   the   product   will   be   damaged.
8.5   After   the   product   is   connected   to   the   power   supply,   please   do   not   touch   the   live   parts   to   avoid   electric
shock.
8.6   This   product   needs   to   cooperate   with   micro-break   to   play   a   short-circuit   protection   function,   otherwise
the   product   will   not   be   able   to   provide   protection   when   a   short-circuit   occurs   in   the   load   of   the   product.
8.7   Since   the   product   has   an   automatic   reset   function,   after   the   product   is   protected   and   activated,   the
load   (electrical   appliances)   should   be   removed   immediately,   and   the   circuit   should   be   checked,   otherwise
the   product   will   frequently   switch   on   the   load   and   disconnect   the   load,   which   will   eventually   damage   the
product   or   electrical   appliances   due   to   frequent   overloads   for   a   long   time.
8.8   The   product   should   be   protected   from   moisture   and   dust   when   it   is   not   used   for   a   long   time.   The
product   should   be   tested   as   described   above   before   using,   and   it   can   be   used   while   it   is   normal.
8.9   This   product   has   no   isolation   function.   Please   disconnect   the   front-level   circuit   breaker   switch   when
repairing   the   circuit.
8.   10   The   zero   line   (N   line)   of   this   product   is   directly   connected   and   has   no   disconnection   function.
8.   11   This   product   has   no   over-current   short-circuit   breaking   capacity.   Please   install   a   small   circuit
breaker   such   as   DZ-47   or   C65   at   the   front   of   the   line   as   over-current   protection.
8.12   If   the   actual   setting   is   different   from   this   manual   due   to   product   upgrade,   please   contact   our
company.   Product   upgrade   will   not   be   notified   separately.


9.   Product   wiring   diagram

 

PNEUTEC.IT, 2023