EDI Technology
With anion cation ionexchange membrane,ion exchange resin,and DC electric to implement ions directed migration.thus
completing water desalination. meanwhile resion regenerate with H and OH from electrolysed water
,so no chemical is needed.
How EDI works
1. Evenly assignwater to the freshwater room, RO enters
the EDI module.
2. The trace ions with RO membrane are adsorbed on the
membrane surface.
3. DC is added to the EDI module at both ends of
electrodes to drive the fresh water chamber of the cation
anion to the corresponding electrode moving to the
dense water chamber.Then the water with high purity is
obtained.
4. Driven by the effects of electric field, a large number
of water molecules are ionized into H
+
and OH
-
, thus
regeneration can be continuously kept
EDI water conditions
Water Source: RO water
Conductivity:≤20μS/cm
Best conductivity: 2-10μS/cm
Maximum Conductivity:≤50μS/cm
PH Value: 6-8
Temperature: 5 -38
Inlet Pressure: 0.2-0.6MPa
Hardness: less than 0.5ppm, (by CaCO
3
)
Si: less than 0.5ppm, (by SiO
2
)