Self-supporting
LV-ABC
L
ines
C
ode:
ABC 0.6/1kV, NFA2X,
AsXS (
n), 1-AES
Standards:
HD 626 S1: 1996 Part
4
-Section
F,
PL WT92/K396, CSN 34761-4F
Construction:
Phase Conductors:
Aluminum conductors with XLPE insulation
.
N
eutral
M
essenger
:
Aluminum conductors
with XLPE insulation
.
Application:
A
e
ri
a
l
B
undled
C
onductors are used
for tributary networks of power buildings
and their internal networks
.
Installation
:
These cables are
not allowed
to
be buried, even in conduits
.
power cable,pvc cable,abc cable,conductor,cable,wiring cable,electric wire,acsr ,flexible cable,spiral cable,power supply cable,copper wire,pvc wire cable,wire cable
Dimensions of phase conductors
Cross
section
|
Conductor
diameter
|
Thickness
of insulation
|
Core
diameter
|
Current
carrying
capacity
|
Breaking
load
|
(mm
²
)
|
min.
|
max.
|
nom.
|
min.
|
min.
|
(A*)
|
(kN)
|
(mm)
|
(mm)
|
(mm)
|
(mm)
|
(mm)
|
16
|
4,6
|
5,1
|
1,2
|
1,00
|
7,8
|
-
|
2,60
|
25
|
5,6
|
6,5
|
1,3
|
1,07
|
10,1
|
107
|
4,17
|
35
|
6,6
|
7,5
|
1,3
|
1,07
|
11,0
|
132
|
5,78
|
50
|
7,7
|
8,6
|
1,5
|
1,25
|
12,5
|
165
|
8,45
|
70
|
9,3
|
10,2
|
1,5
|
1,25
|
14,0
|
205
|
11,32
|
95
|
11,0
|
12,0
|
1,7
|
1,50
|
16,1
|
-
|
15,30
|
120
|
12,5
|
13,5
|
1,8
|
1,60
|
17,6
|
-
|
20,00
|
150
|
13,9
|
15,0
|
1,8
|
1,60
|
18,8
|
-
|
25,00
|
* defined for ambient temperature of 3
5
°C and max. conductor temperature of
8
0°C
Dimensions of neutral messenger conductors
Number of phase cores x cross section
|
Bundle diameter
|
+ public lighting conductors
|
approx.
|
+ neutral cross section
|
|
(mm²)
|
(mm)
|
2 x 16
|
15
|
2 x 25
|
18
|
2 x 35
|
20
|
4 x 16
|
18
|
4 x 25
|
22
|
4 x 35
|
25
|
4 x 50
|
28
|
4 x 70
|
32
|
4 x 70 + 1 x 35
|
36
|
4 x 70 + 2 x 35
|
40
|
4 x 95
|
37
|
4 x 120
|
40
|
4 x 120 + 2 x 35
|
43
|
4 x 150
|
44
|
LV-ABC
L
ines
w
ith
Bare
N
eutral
M
essenger
C
ode:
ABC 0.6/1kV,
Standards:
HD 626 S1: 1996 Part
5
-Section
D,
AMKA (
SFS 2200)
Construction:
Phase Conductors:
Aluminum conductors with XLPE insulation
.
N
eutral
M
essenger
:
Aluminum conductors
Application:
A
e
ri
a
l
B
undled
C
onductors are used for
tributary networks of power buildings and
their internal networks
.
Installation
:
These cables are
not allowed
to
be buried, even in conduits
.
Dimensions of phase conductors
Cross section
|
Conductor diameter
|
Thickness of insulation
|
Core diameter
|
Current carrying capacity
|
Breaking load
|
(mm²)
|
min.
|
tolerance
|
nom.
|
min.
|
min.
|
max.
|
(A*)
|
(kN)
|
(mm)
|
(mm)
|
(mm)
|
(mm)
|
(mm)
|
|
16
|
4,4
|
±0,05
|
1,4
|
-
|
7,1
|
7,3
|
70
|
-
|
25
|
5,9
|
±0,02
|
1,4
|
-
|
8,3
|
9,1
|
95
|
-
|
35
|
6,9
|
±0,02
|
1,6
|
-
|
9,7
|
10,5
|
115
|
-
|
50
|
8,1
|
±0,25
|
1,6
|
-
|
10,8
|
11,8
|
140
|
-
|
70
|
9,7
|
±0,25
|
1,8
|
-
|
12,8
|
13,8
|
180
|
-
|
120
|
12,8
|
±0,30
|
2,0
|
-
|
16,2
|
17,4
|
250
|
-
|
* defined for ambient temperature of 25°C and max. conductor temperature of 70°C
Dimensions of neutral messenger conductors
Cross
section
|
Conductor
diameter
|
Thickness
of insulation
|
Core
diameter
|
Current
carrying
capacity
|
Breaking
load
|
(mm
²
)
|
min.
|
max.
|
nom.
|
min.
|
min.
|
max.
|
(A*)
|
(kN)
|
(mm)
|
(mm)
|
(mm)
|
(mm)
|
(mm)
|
(mm)
|
25
|
5,9
|
±
0,02
|
-
|
-
|
5,5
|
6,3
|
-
|
7,4
|
35
|
6,9
|
±
0,02
|
-
|
-
|
6,5
|
7,3
|
-
|
10,3
|
50
|
8,1
|
±
0,25
|
-
|
-
|
7,6
|
8,6
|
-
|
14,2
|
70
|
9,7
|
±
0,25
|
-
|
-
|
9,2
|
10,2
|
-
|
20,6
|
95
|
11,4
|
±
0,30
|
-
|
-
|
10,8
|
12,0
|
-
|
27,9
|
Dimensions of Cable Bundle
Number of phase cores x cross section
|
Bundle diameter
|
+ neutral cross section
|
approx.
|
(mm²)
|
(mm)
|
1
x 16
+ 25
|
15
|
3
x
16 + 25
|
22
|
4
x
16 + 25
|
22
|
3
x
25 + 35
|
26
|
4 x 25
+ 35
|
26
|
3
x 35
+ 50
|
30
|
3
x 50
+ 70
|
35
|
3
x 70
+ 95
|
41
|
3
x
120
+
95
|
47
|
LV-ABC
L
ines
w
ith
I
nsulated
N
eutral
M
essenger
C
ode:
ABC 0.6/1kV,
Standards:
HD 626 S1: 1996 Part
6
-Section
E,
AMKA (
SFS 2200)
Construction:
Aluminum conductors with XLPE insulation
.
Application:
A
e
ri
a
l
B
undled
C
onductors are used for
tributary networks of power buildings and
their internal networks
.
Installation
:
These cables are
not allowed
to
be buried, even in conduits
.
Dimensions of phase conductors
Cross
section
|
Conductor
diameter
|
Thickness
of insulation
|
Core
diameter
|
Current
carrying
capacity
|
Breaking
load
|
(mm
²
)
|
min.
|
max.
|
nom.
|
min.
|
min.
|
max
|
(A*)
|
(kN)
|
(mm)
|
(mm)
|
(mm)
|
(mm)
|
(mm)
|
|
16
|
4,6
|
5,1
|
1,2
|
-
|
7,0
|
7,8
|
-
|
-
|
25
|
5,8
|
6,3
|
1,4
|
-
|
8,6
|
9,4
|
112
|
-
|
35
|
6,8
|
7,3
|
1,6
|
-
|
10,0
|
10,9
|
138
|
-
|
50
|
7,9
|
8,4
|
1,6
|
-
|
11,1
|
12,0
|
168
|
-
|
70
|
9,7
|
10,2
|
1,8
|
-
|
13,3
|
14,2
|
213
|
-
|
95
|
11,0
|
12,0
|
1,8
|
-
|
14,6
|
15,7
|
258
|
-
|
120
|
12,0
|
13,1
|
1,8
|
-
|
15,6
|
16,7
|
306
|
-
|
150
|
13,9
|
15,0
|
1,7
|
-
|
17,3
|
18,6
|
344
|
-
|
* defined for ambient temperature of
30
°C and max. conductor temperature of
90
°C
Dimensions of neutral messenger conductors
Cross
section
|
Conductor
diameter
|
Thickness
of insulation
|
Core
diameter
|
Current
carrying
capacity
|
Breaking
load
|
(mm
²
)
|
min.
|
max.
|
nom.
|
min.
|
min.
|
max
|
(A*)
|
(kN)
|
(mm)
|
(mm)
|
(mm)
|
(mm)
|
(mm)
|
|
54,6
|
9,2
|
9,6
|
1,6
|
-
|
12,3
|
13,0
|
-
|
16,6
|
70
|
10,0
|
10,2
|
1,5
|
-
|
12,9
|
13,6
|
-
|
20,5
|
95
|
12,2
|
12,9
|
1,6
|
-
|
15,3
|
16,3
|
-
|
27,5
|
* defined for ambient temperature of
30
°C and max. conductor temperature of
90
°C
Dimensions of Cable Bundle
Number of phase cores x cross section
|
Bundle diameter
|
+ public lighting conductors
|
approx.
|
+ neutral cross section
|
|
(mm²)
|
(mm)
|
3 x 25 + 54,6
|
30,0
|
3 x 35 + K x 16 + 54,6
|
33,0
|
3 x 50 + K x 16 + 54,6
|
36,0
|
3 x 70 + K x 16 + 54,6
|
37,5
|
3 x 70 + K x 25 + 54,6
|
40,0
|
3 x 70 + K x 16 + 70
|
41,0
|
3 x 95 + K x 16 + 70
|
44,0
|
3 x 120 + K x 16 + 70
|
46,0
|
3 x 120 + K x 16 + 95
|
47,0
|
3 x 150 + K x 16 + 70
|
48,0
|
3 x 150 + K x 16 + 95
|
49,0
|
Note:
K number of public lighting conductors (K can be equal to 0, 1, 2, or 3)
Packing
Our wokshop
Range of Business:
Cables
Low Voltage Power Cable: 0.6/1kV and Below PVC or XLPE Insulated Power Cable
Medium Voltage Power Cable: 6-35kV XLPE Insulated Power Cable
High Voltage (Extra-high Voltage) Power Cable: 66-500kV XLPE Insulated Power Cable
Bare Conductor and Electrical Wires
Cable Accessories
1~35kv cold shrinkable products
a. Indoor termination
b. Outdoor termination
c. Straight Through Joint
1~35kv heat shrinkable Products
a. Indoor termination
b. Outdoor termination
c. Straight Through Joint
66kv ~500kv Products
a. Porcelain Outdoor termination
b. Compound Sleeve Termination
c. GIS termination ( Assembly, plug-in Type )
d. Premould termination
e. Straight Joint/ Insulation Joint
f. Branch Joint
g. Dry and Y shape Branch Joint
Why choose us?
1. Export to many countries including Iraq, Tanzania and Australia and USA.
2. Best manufacturing and testing equipments imported from Germany, USA and Japan guarantee the best quality with competitive prices.
3. Professional overseas team guarantees you best pre-and-after sale services.
4. Experienced engineers and workers for more than 20 years ensure the quality and customized products.
5. 5S Management to enhance the qualifications of staff and make better service for customers.
6. Near Shanghai and Ningbo Port workshop makes it convenient to delivery on time.