| Bitmap General Specifications and Guarantee Schedule for outdoor silieone rubber termination for 36/66 kv .Single Core XLPE insulated Power Cable with round stranded Copper Conductor 1x630mm2.CU/XLPE/CU(wires+tapes) screen /HDPE sheath | ||||
| No | Description | Unit | PETE requirements | Offered data |
| 1 | Name & country of Manufacturer | HEMG | ||
| 2 | Country of Origin | China | ||
| 3 | Outdoor termination type | Outdoor silicone rubber terminations | Outdoor silicone rubber terminations | |
| 4 | Outdoor termination designation | Prefabricated | ||
| 5 | Standards | Cenelee ho 628/629…iec60..332..502..vde..din | IEC60840 | |
| 6 | Climatic Design | c | (-10)to(55) | (-10)to(55) |
| 7 | Class and form of Conductor | Class 2 rounded stranded &compacted conductor | Class 2 rounded stranded &compacted | |
| 8 | Material of Conductor | Copper | Copper | |
| 9 | Rated voltage | kv | 36/66 | 36/66 |
| 9.1 | Termination suitable to be used with following cables: | Yes | ||
| Conductor: | ||||
| - Cross section | mm ² | 1x630 | 1x630 | |
| - diameter | mm | From 29.5 to 31.5 | From 29.5 to 31.5 | |
| Conductor Screen: | ||||
| - Material | Extruded semi conductive layer | Extruded semi conductive layer | ||
| - Thickness | mm | From0.85 to 1 | From0.85 to 1 | |
| Insulation: | ||||
| - Material | XLPE | XLPE | ||
| - Thickness | mm | 12 | 12 | |
| - Diameter over insulation | mm | From55to58 | From55to58 | |
| Insulation screen: (S.C Layer): | ||||
| - Material | Extruded semi conductive layer | Extruded semi conductive layer | ||
| - Thickness | mm | From0.85 to 1 | From0.85 to 1 | |
| - Thickness of semi-conductive swelling Tape (lapped) | mm | From(0.3 to .5) | From(0.3 to .5) | |
| Metallic screen: | ||||
| - Cross section of earthing cu wires | mm ² | 120 | 120 | |
| - Diameter of cu wire | mm | 1.8 | 1.8 | |
| - thickness of Copper Tape | mm | 0.2 | 0.2 | |
| - Width of Copper Tape | mm | 20 | 20 | |
| - thickness of longitude Swilling Tape | mm | 0.2 | 0.2 | |
| Metallic Shield: | ||||
| - thickness of Comp layer al (Coated Al ) | mm | 0.2 | 0.2 | |
| Outer Protective Sheath (HDPE ST7 ) | ||||
| - Material | HDPE ST7 | HDPE ST7 | ||
| - Thickness of outer Sheath | mm | 4.5 | 4.5 | |
| - Outer diameter of cable | mm | 70 | 70 | |
| 10 | Max. service voltage | kv | 72.5 | 72.5 |
| 11 | Rated frequency | Hz | 50 | 50 |
| 12 | Power frequency with stand voltage (a) | Kv/min | 90kv/30min | 90kv/30min |
| 13 | Partial discharge level | ≤ 10 PC at 1.5 U0 (54kv) | ≤ 10 PC at 1.5 U0 (54kv) | |
| 14 | Impulse with stand voltage 10 x (+)1.2/50us | kv | ± 325 | ±325 |
| 15 | Power freq. with stand voltage (b) | Kv/min | 90kv/15min | 90kv/15min |
| 16 | Load cycling test Cycle:8h heating 16h cooling | According to iec 60840 on accessories | According to iec 60840 on accessories | |
| Conductor temperature | 95 o c-100 o c | 95 o c-100 o c | ||
| 17 | Thermal short circuit current : | KA/1sec | ≥ 31 | ≥ 31 |
| - 1sec/symmetrical fault with conductor temperature as for cable specification | ||||
| 18 | Resistively to mineral oil . Acids. Solvents | Yes | ||
| 19 | Saturated air | Yes | ||
| 20.1 20.2 20.3 | Water conductivity | Yes | ||
| Spray rate | ||||
| Salt tog test | ||||
| 21 | Humidity and congestion test | Kv/h | 42.5 | |
| 22 | Flame resistance test | IEC 332 | IEC 332 | |
| 23 | Submit copies of test reports by independent laboratory | Should be submitted | Yes | |
| 24 | Components ayers and materials of termination and their properties: | Yes | ||
| 24.1 | Lug | mm² | Conductor 630 mm ² CU | Conductor 630 mm²CU |
| 24.2 | Electrical stress control system : | |||
| - indicate shrink ratio properties : | mm | 5-8mm | ||
| Design (shape ) | Cone | |||
| - length | mm | 1000 | ||
| -stress grading ( plot ) | Supplied with products | |||
| 24.3 | Insulation: | |||
| 24.4 | Leakage current insulation system : | Number of sheds(skirts):15 pcs.;Diameter of sheds:210mm;Total extended creepage distance: more than 2250 | ||
| Number of sheds(skirts) | ||||
| Diameter of sheds | mm | |||
| Total extended creepage distance | mm | |||
| 24.5 | Shield. metal continuity CU screen wires Coated Aluminium tape | mm² | Cross section 120 | Cross section 120 |
| 24.6 | - outer sheath (outer cover ) | -indicate shrink ratio | 50% | |
| 24.7 | Submit detailed information and documentation about the components layers and materials of termination and their electrical &non-electrical properties | Provide separately | Yes | |
| 24.8 | Dimensions of termination after completion: | Diameters:220mm;overall length:1500mm | ||
| -Diameters | mm | |||
| - overall length | mm | |||
| 24.9 | Printed on tubes | Mandatory according to condition book | Yes | |
| 24.1 | The applicable range of termination (cross section of conductor) | mm² | The wide range is preferred | 240-2000 |
| 25 | Submit kit contents of termination | Complete list of kit contents with description | Yes | |
| 26 | Submit installation instruction | Provide separately | Yes | |
| 27 | Submit dimension drawing | Provide separately | Yes | |
| 28 | Shelf life | year | 15 | |
| 29 | Submit quality assurance certificates (ISO accreditation) | More certificates are preferable (i.e 9001.14001 etc.) | Yes | |
| 30 | Submit reference list | Provide separately | Yes | |
| 31 | Total weight of termination kit | kg | 25 | |
| 32 | Time of execution of one termination | minute | 480 | |
| 33 | Include any special tools for execution of the termination (if required) with detailed description of tools (with photo/drawings) | optional | None | |
| 34 | Total number of required termination | Qty | 50 | 50 |
| No | Description | Unit | Requirements | Offered data |
| 1 | Name & country of Manufacturer | HEMG | ||
| 2 | Country of Origin | China | ||
| 3 | Joint type | Silicon rubber cable joint | Silicon rubber cable joint | |
| 4 | Joint designation | Prefabricated | ||
| 5 | Standards | Cenelee HO 628/629… IEC 60.332.502.. vde..din | IEC60840 | |
| 6 | Climatic Design | o c | (-10)to(55) | (-10)to(55) |
| 7 | Class and form of Conductor | Class 2 rounded stranded &compacted conductor | Class 2 rounded stranded &compacted | |
| 8 | Material of Conductor | copper | copper | |
| 9 | Rated voltage | kv | 36/66 | 36/66 |
| 9.1 | Termination suitable to be used with following cables: | Yes | ||
| Conductor: | ||||
| - Cross section | mm ² | 1x630 | 1x630 | |
| - diameter | mm | From29.5to31.5 | From29.5to31.5 | |
| Conductor Screen: | ||||
| - Material | Extruded semi conductive layer | Extruded semi conductive layer | ||
| - Thickness | mm | From 0.85 to1 | From 0.85 to1 | |
| Insulation: | ||||
| - Material | XLPE | XLPE | ||
| - Thickness | mm | 12 | 12 | |
| - Diameter over insulation | mm | From55 to58 | From55 to58 | |
| Insulation Screen: (S.C Layer): | ||||
| - Material | Extruded semi conductive layer | Extruded semi conductive layer | ||
| - Thickness | mm | From 0.85 to 1 | From 0.85 to 1 | |
| - Thickness of semi-conductive swelling Tape (lapped) | mm | From(0.3 to0.5) | From(0.3 to0.5) | |
| Metallic Screen: | ||||
| - Cross section of earthing cu wires | mm² | 120 | 120 | |
| - Diameter of cu wire | mm | 1.8 | 1.8 | |
| - thickness of Copper Tape | mm | 0.2 | 0.2 | |
| - Width of Copper Tape | mm | 20 | 20 | |
| - thickness of longitude Swilling Tape | mm | 0.2 | 0.2 | |
| metallic Shield: | ||||
| - thickness of Comp layer al (Coated Al ) | mm | 0.2 | 0.2 | |
| Outer Protective Sheath (HDPE ST7 ) | ||||
| - Material | HDPE ST7 | HDPE ST7 | ||
| - Thickness of outer Sheath | mm | 4.5 | 4.5 | |
| - Outer diameter of cable | mm | 70 | 70 | |
| 10 | Max .service voltage | Kv | 72.5 | 72.5 |
| 11 | Rated frequency | Hz | 50 | 50 |
| 12 | Power frequency | Kv/min | 90kv/30min | 90kv/30min |
| 13 | Partial discharge level | ≤ 10PC at 1.5U0(54kv) | ≤ 10PC at 1.5U0(54kv) | |
| 14 | Impulse withstand voltage 10x(+)1.2/50us | kv | ± 325 | ±325 |
| 15 | Power freq.with stand voltage (b) | Kv/min | 90kv/15min | 90kv/15min |
| 16 | Load cycling test cycle:5 h heating 3 h cooling | 3 cycles | 3 cycles | |
| -conductor temperature | 90 ºC +10 ºC | 90 ºC +10 ºC | ||
| 17 | Thermal short circuit current : | KA/1sec | ≥ 31 | ≥ 31 |
| - 1sec/symmetrical fault with conductor temperature as for cable specification | ||||
| 18 | Resistively to mineral oil . acids. solvents | Yes | ||
| 19 | Humidity and congestion test | Kv/h | 41.8 | |
| 20 | Flame resistance test | IEC 332 | IEC 332 | |
| 21 | Submit copies of test reports by independent laboratory | Should be submitted | Yes | |
| 22 | Components layers and materials of joint and their properties: | |||
| 22.1 | Conductor connector | Bolted or mechanical ( pressure ) | Pressure | |
| 22.2 | Electrical stress control system : | Design (shape ): Stress cone;length:610mm. | ||
| - indicate shrink ratio properties : | mm | 8-12mm | ||
| - Design (shape ) | Cylindrical | |||
| - length | mm | 610 | ||
| -stress grading ( plot ) | Supplied with products | |||
| 22.3 | Insulation: | mm | ||
| Screening | Thickness:0.5 | |||
| 22.4 | Shield. Metal continuity CU screen wires coated Aluminium tape | mm² | Cross section 120 - 130 mm ² | Cross section 120 - 130 mm² |
| 22.5 | Outer sheath ( outer cover ) | Heat shrink tube with adhesive (in one picce ) (heat melt adhesive) | 50% | |
| Indicate shrink ratio | ||||
| 22.6 | Submit detailed information and documentation about the components layers and materials of termination and their electrical &non-electrical properties | Provide separately | Yes | |
| 22.7 | Dimensions of termination after completion: | Diameters:200mm;overall length:1500mm | ||
| -Diameters | mm | |||
| - overall length | mm | |||
| 22.8 | - printed on all heat shrink tubes | Mandatory according to condition book | Yes | |
| 22.9 | The applicable range of joint ( cross section of conductor ) | mm² | The wide range is preferred | 240-2000 |
| 23 | Submit kit contents of joint | Complete list of kit contents with description | Yes | |
| 24 | Submit installation instruction | Provide separately | Yes | |
| 25 | Submit dimensions drawing | Provide separately | Yes | |
| 26 | Shelf life | Year | 15 | |
| 27 | Submit test reports of all materials of joint kit | Provide separately | Yes | |
| 28 | Submit quality assurance certificate ( ISO accreditation ) | More certificates are preferable ( i.e 9001 . 14001 ete ) | Yes | |
| 29 | Submit reference list | Provide separately | Yes | |
| 30 | Total weight of joint box | Kg | 85 | |
| 31 | Time of execution of one joint | Minute | 500 | |
| 32 | Include any special tools for execution of the joint ( if required) with detailed description of tools ( with photo/drawings) | Optional | None | |
| 33 | Total joints | Qty | 200 | 200 |