| Model | ND110-1010 | ND110-1020 | ND110-1030 | ND110-1040 | ND110-1050 | ND110-1060 | ND110-1100 | ND110-1200 | |
| DC input | |||||||||
| Rated Input Voltage | 110 VDC | ||||||||
| Rated Input Current | 9.09A | 19A | 27A | 36A | 45A | 54A | 91A | 182A | |
| DC Input Voltage Range | 88~132Vdc | ||||||||
| Bypass Utility Input | |||||||||
| AC Input Voltage | 220Vac±20%, 50/60Hz ±10% | ||||||||
| Rated Input Current | 4.5A | 9A | 13.5A | 18A | 22.7A | 27A | 45A | 91A | |
| Bypass Transfer Time | ≤4 ms | ||||||||
| AC Output | |||||||||
| Rated Capacity | 1KVA | 2KVA | 3KVA | 4KVA | 5KVA | 6KVA | 10KVA | 20KVA | |
| Rated Output Power | 0.8KW | 1.6KW | 2.4KW | 3.2KW | 4KW | 4.8KW | 8KW | 16KW | |
| Rated Output Voltage and Frequency | 220V AC , 50/60Hz | ||||||||
| Rated Output Current | 4.5A | 9A | 13.5A | 18A | 22.7A | 27A | 45A | 91A | |
| Output Voltage Regulation | 220Vac±2% | ||||||||
| Output Frequency Regulation | 50/60Hz ±1% | ||||||||
| THD | ≤3% | ||||||||
| Dynamic Response (Load 0←→100%) | 5% | ||||||||
| Power Factor | 0.8 | ||||||||
| Overload | 150%, 60s | ||||||||
| Crest Factor | 3:01 | ||||||||
| Efficiency at Rated Load | 90% | ||||||||
| Environment | |||||||||
| Insulation Strength (Between Input & Output) | 1500V AC , 1min | ||||||||
| Noise (1m) | ≤50dB | ||||||||
| Temperature | -10ºC~+50ºC | ||||||||
| Humidity | 0~90%, no condensation | ||||||||
| Altitude (m) | ≤2000 | ||||||||
| Physical | |||||||||
| Size (W* D * H, mm) | 440×450×177 | 440×500×221.5 | 343*630*700 | ||||||
| Type | Rack Type | Tower Type | |||||||
| Protection | DC input reversely protection, DC input under voltage,over voltage, overload, short circuit, over temperature | ||||||||